6.3.2.8

Enable logic

If, when commissioning, you interconnected telegrams, then these interconnections are
displayed in the "Enable logic" screen form. Further specification is not required.
If, when commissioning, you did not specify any telegram types, then you must interconnect
the required signal sources in the "Enable logic" screen form.
Interconnecting signal sources
1. Connect the signal source for the "Infeed operation" (p0864) command.
2. Connect the signal source for the "OFF1 (low active)" command (p0840).
This command corresponds to control word 1 bit 1 (STW1.1) in the PROFIdrive profile.
3. Connect the 1st signal source for the "OFF2 (low active) signal source 1" command
(p0844).
This command corresponds to control word 1 bit 1 (STW1.1) in the PROFIdrive profile.
4. Connect the 2nd signal source for the "OFF2 (low active) signal source 2" command
(p0845).
5. Connect the 1st signal source for the "OFF3 (low active) signal source 1" command
(p0848).
This command corresponds to control word 1 bit 2 (STW1.2) in the PROFIdrive profile.
6. Connect the 2nd signal source for the "OFF3 (low active) signal source 2" command
(p0849).
This command corresponds to control word 1 bit 2 (STW1.2) in the PROFIdrive profile.
7. Interconnect the signal source for the "Enable operation" command (p0852).
This command corresponds to control word 1 bit 3 (STW1.3) in the PROFIdrive profile.
Getting Started, 12/2018, 6SL3097-5AG30-0BP0
"Infeed unit > Parameters > Basic parameterization > Enable logic"
Performing basic parameterization