Fundamental safety instructions
1.1 General safety instructions
Active implant malfunctions due to electromagnetic fields
Inverters generate electromagnetic fields (EMF) in operation. People with active implants in
the immediate vicinity of this equipment are at particular risk.
• As the operator of an EMF-emitting installation, assess the individual risks of persons
Unexpected movement of machines caused by radio devices or mobile phones
When radio devices or mobile phones with a transmission power > 1 W are used in the
immediate vicinity of components, they may cause the equipment to malfunction.
Malfunctions may impair the functional safety of machines and can therefore put people in
danger or lead to property damage.
• If you come closer than around 2 m to such components, switch off any radios or mobile
• Use the "SIEMENS Industry Online Support app" only on equipment that has already
NOTICE
Damage to motor insulation due to excessive voltages
When operated on systems with grounded line conductor or in the event of a ground fault in
the IT system, the motor insulation can be damaged by the higher voltage to ground. If you
use motors that have insulation that is not designed for operation with grounded line
conductors, you must perform the following measures:
• IT system: Use a ground fault monitor and eliminate the fault as quickly as possible.
• TN or TT systems with grounded line conductor: Use an isolating transformer on the line
Fire due to inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating of components with subsequent
fire and smoke. This can cause severe injury or even death. This can also result in
increased downtime and reduced service lives for devices/systems.
• Ensure compliance with the specified minimum clearance as ventilation clearance for
20
WARNING
with active implants. The following clearances are usually adequate:
– No clearance to closed control cabinets and shielded MOTION-CONNECT supply
cables
– Forearm length (approx. 35 cm clearance) to distributed drive systems and open
control cabinets
WARNING
phones.
been switched off.
side.
WARNING
the respective component.
Getting Started, 12/2018, 6SL3097-5AG30-0BP0