Revising The Configuration - Siemens SINAMICS S120 Getting Started

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
5.6 Alternative: Loading the configuration of the drive into the project
4. Select the entry "Accessible device [169.254.11.22]" and right-click in the selected line.
The list of the possible options/commands appears.
5. Select the command "Upload device as new station".
Result
The configuration is loaded from the drive into the project.
5.6.2

Revising the configuration

Optimally, all components are transferred specified to the device configuration during an
automatic configuration and do not have to be subsequently specified or supplemented. If
this is the case, a message is shown in the message display that the automatic device
configuration has been performed without error.
If, however, not all components of the drive could be read out by the automatic configuration,
although they do exist physically, the components are created unspecified in the device
view. The missing specification must therefore be added in the device configuration.
Specifying unspecified components
To specify, proceed as follows:
1. Click in the inner white area of the unspecified component envelope.
The area is shown as selected.
2. Open the Inspector window if it has still not been opened or displayed.
3. In the secondary navigation of the Inspector window, select "... - Selection".
A selection of the available components is displayed on the right in "... - Selection".
4. Select the component.
106
Getting Started, 12/2018, 6SL3097-5AG30-0BP0