Commissioning
5.4 Creating a project offline in Startdrive
Additional display or entry fields are now unhidden depending on the respective filter
selected.
Figure 5-19
6. Now parameterize the associated detailed settings for the selected filter.
Result
You have performed the detail settings for a selected Power Module or Motor Module.
5.4.4.4

Connecting several modules in parallel

In Startdrive, several Power Modules or several Motor Modules respectively can be
connected in parallel in vector control. During commissioning, power units connected in
parallel are treated like a power unit on the line or motor side. With parallel connection, the
parameter display for the actual values changes only slightly. Suitable "total values" are
derived from the individual values of the power units.
Functionality of the parallel connection is identical for Motor Modules and Power Modules.
Procedure
A parallel connection using a Motor Module as an example is shown below.
1. Open "Motor Modules" in the hardware catalog.
2. If you have not yet inserted a Motor Module in the device configuration, drag the required,
non-specified Motor Module into the device view and specify it (see Chapter "Inserting
and specifying a Motor Module (Page 78)").
84
Example: Power Module additional data
Getting Started, 12/2018, 6SL3097-5AG30-0BP0