Commissioning
5.4 Creating a project offline in Startdrive
When first switched on with a new/modified network, an automatic controller setting must be
implemented using the line and DC link identification routine (p3410). While the identification
routine is running, it is not permissible for other loads to be switched in/switched out.
Procedure
1. Select the infeed in the device view and open the Inspector window.
2. Select the "Line Module details > Line Module settings" menu in the Inspector window.
In the screen form, the following setting options are displayed:
Figure 5-10
3. In order to parameterize the device supply voltage, click the
data/operating mode" entry.
The "Line data/operating mode" screen form opens:
Figure 5-11
76
Example: Detailed settings for infeed for ALM
Example: Line data/operating mode for ALM
icon next to the "Line