Siemens SINAMICS S120 Getting Started page 155

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Setting the technological application and selection of the motor data identification
1. Select one of the following applications in the "Technology application" (p0500) drop-
down list:
– [0] Standard drive (VECTOR)
– [1] Pumps and fans
– [2] Encoderless control down to f = 0 (passive loads)
– [3] Dynamic response in the field-weakening range
– [4] Approach with high breakaway torque
– [5] High load inertia
2. In the drop-down list "Motor data identification and rotating measurement" (p1900), select
how the motor data identification is to be carried out for a stopped motor:
– [0] Disabled
– [1] Motor data ident. (standstill) and speed controller opt.
– [2] Motor data identification (standstill)
Motors from the motor list
For motors with DRIVE-CLiQ interface or motors from the motor list (see Chapter "Inserting
and specifying motors from the motor list (Page 88)"), no additional entries are required
when automatically calculating the motor/controller parameters.
Third-party motors
Motor and controller parameters must first be calculated for third-party motors and motors
that are not in the motor list.
Getting Started, 12/2018, 6SL3097-5AG30-0BP0
Performing basic parameterization
6.3 Drive axes
153

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents