Line Data / Operating Mode - Siemens SINAMICS S120 Getting Started

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Function module
Supplementary closed-loop control (r0108.3)
Dynamic grid support (r0108.7)
Grid droop control (r0108.12)
Recorder (r0108.5)
Line transformer (r0108.4)
Supplementary cosinus phi module (r0108.10)
Activating a function module
1. To activate a function module, click on the required function module (e.g. master/slave).
Repeat this step for all additional function modules that you wish to activate.
2. Save the project to back up the settings.
6.2.3

Line data / operating mode

You set the most important parameters for the operation of an infeed in the function view of
the "Line data / operating mode" screen form. The corresponding parameters are displayed
depending on the infeed type.
Getting Started, 12/2018, 6SL3097-5AG30-0BP0
"Infeed unit > Parameters > Basic parameterization > Line data/operating mode"
Explanation
For applications with asymmetrical line voltages: A negative se-
quence system current controller is used to balance the line cur-
rents and reduce the DC link ripple.
For applications with resonance effects in the current or the filter
voltage (e.g. in line systems with low short-circuit power ratings).
Freely parameterizable band-pass filters for resonance damping.
For power generation applications in power grids: Functions for grid
support with fault ride-through and line monitoring (incl. active anti-
islanding) according to the applicable grid codes.
Installation, synchronization and operation of island grids: Control of
line frequency and line voltage in single operation or together with
other generators.
Function to record hardware-related fault events
For power generation applications: Magnetization of a transformer
to limit the inrush current when the line system is connected. Com-
pensation of direct current components and voltage drops at the
transformer in conjunction with dynamic grid support or grid droop
control.
Precise cos(Phi) determination based on fundamental current and
voltage components with BICO-interconnectable input variables (in
contrast to power factor r0038).
Performing basic parameterization
6.2 Infeed unit
127