Measuring Sockets T0, T1, T2 - Siemens SINAMICS S120 Manual

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

9.21.9

Measuring sockets T0, T1, T2

Table 9- 40
Connector
PCB plug connector from Phoenix Contact, type: ZEC 1.0/ 4-ST-3.5 C1 R1.4, order number: 1893708
Note
Cable cross-section
The measuring socket contacts are only suitable for cable cross-sections of 0.2 mm
1 mm
Note
Using the measuring socket contacts
The measuring socket contacts support commissioning and diagnostic functions. It must not
be connected for normal operation.
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
Measuring sockets T0, T1, T2
Socket
T0
T1
T2
M
.
2
Function
Measuring socket 0
Measuring socket 1
Measuring socket 2
Ground
9.21 K90, Control Unit CU320-2 DP
Technical data
Voltage: 0 ... 5 V
Resolution: 8 bits
Load current: max. 3 mA
Continuous short-circuit proof
The reference potential is terminal M
Options
to
2
403