Performing basic parameterization
6.2 Infeed unit
Figure 6-5
The representation of this screen form is dependent upon the respective Line Module being
used:
Setting
Device supply volt-
age
DC-link voltage
setpoint default
setting
Supply/DC-link iden-
tification
Operating mode for
ALM
Setting the line data and operating mode
The parameters in this screen form are assigned default values when creating the device.
1. Enter a value for the device supply voltage in the "Device supply voltage" field (p0210).
2. To activate the line/DC link identification, in the drop-down list "Supply/DC link
identification", select option "On".
128
Example: Line data/operating mode for an Active Line Module
ALM
SLM
x
x
x
x
BLM
Explanation
x
x
-
x
-
The value in this field (p3510) is deter-
mined automatically from the defined
operating voltage.
x
-
If the line supply / DC-link identification
has already been performed once, then
the value is preset to "OFF".
-
-
Presetting of the operating mode is de-
pendent upon the operating voltage of
the ALM:
≤ 415 V
Mode) active
≤ 415 V
Mode) active
Getting Started, 12/2018, 6SL3097-5AG30-0BP0
= Unregulated Udc (Active
eff
= Udc Regulated Udc (Active
eff