Commissioning
5.4 Creating a project offline in Startdrive
Preconditions
● A project has been created.
● The Control Unit is inserted in the device configuration.
● An infeed is inserted into the device configuration.
Alternatively: A Motor Module of drive object type VECTOR is available.
Procedure
1. Open "Supplementary system components > Voltage Sensing Modules" in the hardware
catalog.
2. Select the "Voltage Sensing Module VSM10" in the device overview.
3. Drag the "Voltage Sensing Module VSM10" into the device view on the infeed unit, or
alternatively on a VECTOR-type Motor Module.
Result
The VSM10 is inserted in the selected drive object. The required DRIVE-CLiQ connections
are drawn automatically.
The VSM10 does not have to be specified any further.
Operation of several VSMs per Line Module
Depending on the type and design, a maximum of 3 VSMs (e.g. Active Line Modules in
Chassis design) can be added to a Line Module via drag & drop. You can find further
information on the rules for operating multiple VSMs per Line Module in the SINAMICS S120
Function Manual Drive Functions.
Note
Activating the "Line transformer" function module
If you operate several VSMs on one Line Module, you must activate the "Line transformer"
function module in the basic parameterization of the Line Module.
Note
Deleting additional Voltage Sensing Modules
If you delete additional VSMs, you must deactivate the "Line transformer" function module in
the basic parameterization. Otherwise the computing power of the Control Unit may be
adversely affected.
100
Getting Started, 12/2018, 6SL3097-5AG30-0BP0