– TM120 Terminal Module
– TM150 Terminal Module
2. Select the Terminal Module in the device overview.
3. Drag the Terminal Module to the device view.
The DRIVE-CLiQ connections are drawn automatically.
5.4.7.3
Adding a Terminal Board
Terminal Board TB30 is a terminal module with which it is possible to expand the interfaces
of the Control Unit. The Terminal Board is inserted into the option slot of the Control Unit.
The Terminal Board does not have to be specified any further.
Preconditions
● A project has been created.
● A Control Unit is contained in the device configuration.
● No Communication Board CBE20 is contained in the device configuration.
TB30 and CBE20 cannot be created simultaneously in the device configuration.
Procedure
1. Open "Additional system components > Terminal Boards" in the hardware catalog.
The "TB30 Terminal Board" entry is displayed.
2. Select the TB30 Terminal Board in the device overview.
3. Drag the Terminal Board to the device view.
5.4.7.4
Adding the VSM10 Voltage Sensing Module
Voltage Sensing Modules (VSM) can be used for 2 different drive objects:
● Infeed unit
Is used for voltage measurement, e.g. for the "mains transformer" function.
A VSM10 allows an exact recording of the line voltage curve and supports the fault-free
operation of the Line Modules in unfavorable network conditions.
● Motor Modules of the VECTOR type
Required for the functions "synchronize" and "flying restart".
Note
Voltage Sensing Modules are inserted automatically with Active Line Modules or Smart Line
Modules in Chassis design.
Getting Started, 12/2018, 6SL3097-5AG30-0BP0
5.4 Creating a project offline in Startdrive
Commissioning
99