Installation
4.3 Connecting the inverter to PROFINET
Further information on the operation as Ethernet nodes can be found in the Function Manual
"Fieldbuses".
Further information on PROFINET
Further information on PROFINET can be found on the Internet:
●
(http://w3.siemens.com/mcms/automation/en/industrial-
communications/profinet/Pages/Default.aspx)
●
(https://support.industry.siemens.com/cs/ww/en/view/19292127)
4.3.1
Connecting the PROFINET interface
Industrial Ethernet Cables and cable length
Listed in the table below are the recommended Ethernet cables.
Table 4- 16
Cable type
Industrial Ethernet FC TP Standard Cable GP 2 x 2
Industrial Ethernet FC TP Flexible Cable GP 2 x 2
Industrial Ethernet FC Trailing Cable GP 2 x 2
Industrial Ethernet FC Trailing Cable 2 x 2
Industrial Ethernet FC Marine Cable 2 x 2
Cable screening
The screen of the PROFINET cable must be connected with the protective earth. The solid
copper core must not be scored when the insulation is removed from the core ends.
4.3.2
What do you have to set for communication via PROFINET?
Configuring PROFINET communication in the I/O controller
You require the appropriate engineering system to configure PROFINET communication in
the IO controller.
If required, load the GSDML file of the inverter into the engineering system.
74
Overview of the manuals (Page 343)
PROFINET – the Ethernet standard for automation
PROFINET system description
Recommended PROFINET cables
Max. length be-
tween devices
100 m (328 ft)
85 m (278 ft)
85 m (278 ft)
85 m (278 ft)
85 m (278 ft)
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Article Number
6XV1840-2AH10
6XV1870–2B
6XV1870–2D
6XV1840–3AH10
6XV1840–4AH10