Setting Parameters With The Bop Or Aop - Siemens SED2 series Operating Instructions Manual

Variable speed drives
Hide thumbs Also See for SED2 series:
Table of Contents

Advertisement

Changing P0004 –
parameter filter function
Changing an indexed
value under P1082 –
setting the maximum
motor frequency
Siemens Building Technologies
HVAC Products
5.4.4.2

Setting parameters with the BOP or AOP

The following describes how to change parameter P1082. Use this description as a
guide to setting all other parameters with the BOP.
Step
1
Press
to access the parameters.
2
Press
until P0004 is displayed.
3
Press
to access the parameter value level.
4
Press
or
5
Press
to confirm and save the value.
6
Only the motor parameters are now visible for the user.
Step
1
Press
to access the parameters.
2
Press
until P1082 is displayed.
3
Press
to access the parameter value level.
4
Press
or
to display the required value.
5
Press
to confirm and save the value.
6
Press
to return to P0010.
7
Press
to access the parameter value level P0010.
8
Press
to restore the value to P0010 = 0.
Press
to save the parameter and exit the parameter value
9
level.
10
Press
until r0000 is displayed.
Press
to revert to the standard motor display (as defined
11
by the customer).
SED2 variable speed drives
Commissioning
Action
to display the required value.
Action
Resulting display
Resulting display
2
P(1)
Hz

P(1)
Hz

P(1)
Hz
2
P(1)
Hz
49/126
CM1U5192en
01.2002