How To Control The Frequency Converter; Function Codes Supported By Modbus Rtu - Danfoss VLT Compressor Drive CDS 803 Design Manual

Hide thumbs Also See for VLT Compressor Drive CDS 803:
Table of Contents

Advertisement

RS485 Installation and Set-...
Bus
Bus
address
register
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
7
7
8
9
9
10
19
20
29
30
Table 7.18 Address/Registers
1) Value written in the Modbus RTU telegram must be 1 or less than the register number. For example, Read Modbus Register 1 by writing value 0
in the telegram.
7.8.9 How to Control the Frequency
Converter
This section describes codes which can be used in the
function and data fields of a Modbus RTU telegram.
60
VLT
PLC
Content
1)
register
40001
Reserved
40002
Reserved
40003
Reserved
40004
Free
40005
Free
40006
Modbus configuration
40007
Last fault code
40008
Last error register
40009
Index pointer
40010
Parameter 0-01 Language
40020
Parameter 0-02 Motor Speed
Unit
40030
Parameter 0-03 Regional
Settings
Danfoss A/S © 12/2015 All rights reserved.
®
Compressor Drive CDS 803
Access
Description
Reserved for legacy frequency converters VLT
VLT
Reserved for legacy frequency converters VLT
VLT
Reserved for legacy frequency converters VLT
VLT
Read/Write
TCP only. Reserved for Modbus TCP
(parameter 12-28 Store Data Values and
parameter 12-29 Store Always - stored in, for example,
EEPROM).
Read only
Fault code received from parameter database, refer to
WHAT 38295 for details.
Read only
Address of register with which last error occurred, refer
to WHAT 38296 for details.
Read/Write
Sub index of parameter to be accessed. Refer to WHAT
38297 for details.
Dependent on
Parameter 0-01 Language (Modbus register = 10
parameter
parameter number)
access
20 bytes space reserved for parameter in Modbus map.
Dependent on
Parameter 0-02 Motor Speed Unit
parameter
20 bytes space reserved for parameter in Modbus map.
access
Dependent on
Parameter 0-03 Regional Settings
parameter
20 bytes space reserved for parameter in Modbus map.
access
7.8.10 Function Codes Supported by
Modbus RTU
Modbus RTU supports use of the following function codes
in the function field of a telegram.
Function
Read coils
Read holding registers
Write single coil
Write single register
Write multiple coils
Write multiple registers
Get comm. event counter
Report slave ID
Table 7.19 Function Codes
®
2800.
®
2800.
®
2800.
Function code (hex)
1
3
5
6
F
10
B
11
®
5000 and
®
5000 and
®
5000 and
MG18N202