Danfoss VLT Automation Drive FC 360 Programming Manual page 99

Table of Contents

Advertisement

Parameter Descriptions
14-20 Reset Mode
Option:
Function:
[2]
Automatic reset
x 2
[3]
Automatic reset
x 3
[4]
Automatic reset
x 4
[5]
Automatic reset
x 5
[6]
Automatic reset
x 6
[7]
Automatic reset
x 7
[8]
Automatic reset
x 8
[9]
Automatic reset
x 9
[10] Automatic reset
x 10
[11] Automatic reset
x 15
[12] Automatic reset
x 20
[13] Infinite auto
Select [13] Infinite Automatic Reset for
reset
continuous resetting after tripping.
[14] Reset at power-
up
14-21 Automatic Restart Time
Range:
Function:
10 s
[0 - 600
Enter the time interval from trip to start of the
*
s]
automatic reset function. This parameter is
active when parameter 14-20 Reset Mode is set
to [1] - [13] Automatic reset.
14-22 Operation Mode
Option:
Function:
Specify normal operation, perform tests, or
initialise all parameters except for
parameter 15-03 Power Up's,
parameter 15-04 Over Temp's, and
parameter 15-05 Over Volt's. This function is
only active when the power is cycled to the
frequency converter.
[0]
Normal
Normal operation with motor selected.
operation
*
[2]
Initiali-
Reset all parameter values to default settings,
sation
except for parameter 15-03 Power Up's,
parameter 15-04 Over Temp's, and
parameter 15-05 Over Volt's. The frequency
converter resets during the next power-up.
MG06C602
Programming Guide
14-24 Trip Delay at Current Limit
Range:
60 s
*
60 s]
14-25 Trip Delay at Torque Limit
Range:
60 s
*
60 s]
14-27 Action At Inverter Fault
Option:
[0]
Trip
[1]
Warning Runs the protection filters normally.
*
14-28 Production Settings
Option:
[0]
*
[1]
[3]
14-29 Service Code
Range:
0
[0 - 0x7FFFFFFF ]
*
4.13.4 14-3* Current Limit Control
The frequency converter features an integral current limit
controller, which is activated when the motor current, and
thus the torque, is higher than the torque limits set in
parameter 4-16 Torque Limit Motor Mode and
parameter 4-17 Torque Limit Generator Mode.
When the current limit is reached during motor operation
or regenerative operation, the frequency converter tries to
reduce torque below the preset torque limits as quickly as
possible without losing control of the motor.
Danfoss A/S © 7/2015 All rights reserved.
Function:
[0 -
Enter the current limit trip delay in seconds. When
the output current reaches the current limit
(parameter 4-18 Current Limit), a warning is
triggered. When the current limit warning has
been continuously present for the period specified
in this parameter, the frequency converter trips. To
run continuously in current limit without tripping,
set the parameter to 60 s=Off. Thermal monitoring
of the frequency converter remains active.
Function:
[0 -
Enter the torque limit trip delay in seconds. When
the output torque reaches the torque limits
(parameter 4-16 Torque Limit Motor Mode and
parameter 4-17 Torque Limit Generator Mode), a
warning is triggered. When the torque limit
warning has been continuously present for the
period specified in this parameter, the frequency
converter trips. Disable the trip delay by setting
the parameter to 60 s=Off. Thermal monitoring of
the frequency converter remains active.
Function:
Select how the frequency converter reacts when
an overvoltage or grounding fault occurs.
Disables the protection filters and trips at the first
fault.
No action
Service reset
Software Reset
Function:
For internal use only.
4
Function:
97
4