Room Sensor Parameters - Lennox Prodigy 2.0 Application Manual

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

2.2.8.

Room Sensor Parameters

Any of the parameters listed in table 7, can be directly modified using the following method:
Go to SETTINGS > RTU OPTION > EDIT PARAMETER =
Control Parameter
P
Screen Name
63
HT ELEC STG UP TMR
64
HT ELEC STG DWN TMR
74
HT GAS STG UP TMR
75
HT GAS STG DWN TMR
101
CL STG 2 STGUP TIME
102
CL STG 3 STGUP TIME
103
CL STG 4 STGUP TIME
104
CL STAGE DOWN TIME
133
ZONE SENS STRTUP DLY
Table 7. Room Sensor Parameter Summary
Short Description
Min.
Electric Heat
Electric Heat Maximum
Lower Stage Run Time in
0
Room Sensor
Applications
Electric Heat Time Delay
for Lower Stage
0
Termination Following
Higher Stage Termination
Gas Heat
Gas Stage Up Timer
0
Gas Stage Down Timer
0
Cooling
Maximum Stage 1
Cooling Time Before Call
0
for Stage 2 Cooling
Maximum Stage 2
Cooling Time Before Call
0
for Stage 3 Cooling
Maximum Stage 3
Cooling Time Before Call
0
for Stage 4 Cooling
Cooling Stage Down
0
Time
Room Sensor Start-up
2
Delay
Control Value
Unit
Default
Max.
912
3600
Sec
0
3600
Sec
912
3600
Sec
0
3600
Sec
912
3600
Sec
912
3600
Sec
912
3600
Sec
912
3600
Sec
General
2
30
Min
Page 12
Description
Stage up timer. The maximum time that
lower stage runs before calling next
heat stage. Used in room sensor ap­
plications.
Disabled if set to 0.
Time delay before a lower stage turns
off following a higher stage termination.
Used in room sensor applications.
Stage-up timer. The maximum time that
lower stage runs before calling next
heat stage. Used in room sensor ap­
plications.
Disabled if set to 0.
Time delay before a lower stage turns
off following a higher stage termination.
Used in room sensor applications.
Stage 2 stage up timer. The maximum
time that cooling stage 1 runs before
calling cooling stage 2.
Used in room sensor applications.
Disabled if set to 0.
Stage 3 stage up timer. The maximum
time that cooling stage 2 runs before
calling cooling stage 3.
Used in room sensor applications.
Disabled if set to 0.
Stage 4 stage up timer. The maximum
time that cooling stage 3 runs before
calling cooling stage 4.
Used in room sensor applications.
Disabled if set to 0.
Time delay before a lower stage turns
off following a higher stage termination.
Used in room sensor applications.
Delay on any power-up or reset. During
the delay, no blower, heating, or cooling
operation will occur.
May be used to stagger unit start-ups.
Does NOT delay demands in thermo­
stat mode.
Zone Sensor Start-up Delay is termin­
ated if message from Comfort Sensor
or NCP is received.