Lennox Prodigy 2.0 Application Manual page 144

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

ALARM
ALARM
TYPE
TYPE
CODES
CODES
DISPLAY MESSAGE
ADVANCE AIRFLOW DAMPER PRESSURE
143
ALARM
ERROR.
144 - 145 RESERVED
146
ALARM
SERVICE LOGGED
147
ALARM
OA DAMPER ERROR
ALARM(148) ADVANCE AIRFLOW CONFIG
148
ALARM
ERROR
OUTDOOR AIR DIFF PRESSURE SENSOR
149
ALARM
ERROR
NOT ECONOMIZING WHEN OUTDOOR AIR IS
150
ALARM
SUITABLE
ECONOMIZING WHEN OUTDOOR AIR IS NOT
151
ALARM
SUITABLE
152 - 164
RESERVED
165
ALARM
ECONOMIZER NOT CONFIGURED
CAI PRESSURE SWITCH STUCK CLOSED ­
166
ALARM
GV1
CAI PRESSURE SWITCH STUCK CLOSED ­
167
ALARM
GV2
COMBUSTION AIR SW NOT OPEN LOCKOUT ­
168
ALARM
GV1
COMBUSTION AIR SW NOT OPEN LOCKOUT ­
169
ALARM
GV2
170
ALARM
POWER EXHAUST NOT CONFIGURED
171
ALARM
POWER EXHAUST CONFIGURATION ERROR
ADVANCED AIR FLOW CONTROL NOT
172
ALARM
CONFIGURED
173
ALARM
AIR FLOW SWITCH CONFIG ERROR
ZONE (ROOM) BYPASS DAMPER CONFIGUR­
174
ALARM
ATION ERROR
INVALID LOAD SHEDDING INPUT
175
ALARM
CONFIGURATION
SBUS RECEIVED AN OBSOLETE M3
176
ALARM
COMMAND
177
ALARM
MODEL NUMBER NOT DEFINED
178 - 181
RESERVED
TABLE 66. PRODIGY 2.0 ALARM CODES
Event Action
Outdoor air differential pressure sensor value not in valid range. Might be tubing problem or high return duct resistance.
Service event logged
During free cooling damper is not modulating.
Economizer should be installed and blower should be ECM type.
Check outdoor air damper differential pressure sensor and wiring.
May be due to the damper motor being unplugged or disconnected.
my be due to damper motor being blocked open and not closing.
configuration id 1, position 2 is set to u. select applicable option using setup/install wizard.
This alarm will occur when the combustion air pressure switch (S18) is detected as closed immediately after the furnace
demand relay is energized and before the combustion air blower is energized. Gas valve 1.
This alarm will occur when the combustion air pressure switch (S45) is detected as closed immediately after the furnace
demand relay is energized and before the combustion air blower is energized. Gas valve 2.
System locked out due to S45 switch closed and a specific number occurrences detected based on Parameter 72 (MAX
CAI NO PRF OCC) setting during a single cycle.
Configuration ID 1, position 3 is set as U (unconfigured).
Configuration ID 1, position 4 is set correctly. if position 3 is configured then position 4 must be also.
If Configuration ID 1, position 6 - blower VFD bypass is set to A or M, then Configuration ID 2, position 1 must be set to C
or D.
Verify that Configuration ID 2, position 1 is set correctly.
Room bypass damper operation is only compatible with cab blowers. prodigy will only allow zone bypass unit operation if
configuration ID1 is set to installed for units with B or T type blowers. alarm will automatically clear when configuration
conflict is corrected.
Alarm will occur if load shedding input is shared with other optional devices or inputs, for example - global, blower
overload, drain pan overflow, etc.
This alarm occurs when a SBUS master device sends a M2 style command to the M3 unit controller. The alarm is
immediately cleared and a history of the event is stored.
missing model configuration data. run setup > install and complete model number information.