Discharge Air Control - Lennox Prodigy 2.0 Application Manual

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

10. Discharge Air Control

10.1. Cooling
The discharge air control cooling option automatically cycles up to 4-stages of cooling to maintain a discharge air control
cooling set point.
When an economizer is installed, adjust free cooling set point Parameter 159 approximately 2 degrees lower than
Discharge Air Control Cooling set point. This will allow free cooling to operate before Discharge Air Control Cooling
energizes compressors.
Refer to figure 13 for Discharge Air Control Cooling cooling stages.
Adjust Parameter 111 to option 4 to enable discharge air control cooling.
Discharge air sensor RT6 must be moved to the supply air duct, preferably after a 90 degree branch of the main duct.
Discharge Air Control Cooling is initiated by an input in one of three ways:
1. Y1 input from an external device— If the M3 Unit Controller is configured for wired thermostat.
Go to SETTINGS > CONTROL > CONTROL TYPE = WIRED THERMOSTAT.
2. Cooling demand while in RTU STANDALONE mode:
Go to SETUP > NETWORK INEGRATION > NETWORK = RTU STANDALONE > OCC BLOWER MODE = > BACK
UP MODE = > and continue to answer questions concerning heating and cooling setpoints.
3. Cooling demand while in room sensor mode:
Go to SETUP > NETWORK INEGRATION > NETWORK = (L CONNECTION, LONTALK OR BACNET) > any
additional network settings > CONTROL MODE = ROOM SENSOR > and continue to answer questions concerning
network sensor type, OCC blower mode and backup mode.
C1 = Cooling Stage 1
C2 = Cooling Stage 2
C3 = Cooling Stage 3
C4 = Cooling Stage 4
55°F Default Occupied
Discharge Air Control
Cooling Set point
Parameter
180
Figure 13. Discharge Air Control Cooling Stages - Default Values Shown
IMPORTANT
61
60
59
58
°
°
55
F + 2
F Diff
Parameter 180 +
57
Parameter 185
ON
C2
56
55
ON
54
C1
53
55
OFF
52
Parameter 180 + Parameter
185 - Parameter 182
51
OFF
50
55°F - 5°F
Parameter 180 -
Parameter 182
Parameter 181
Unoccupied DACC_SP
Parameter 183
DAC Cooling Stage-Up Delay 3 minutes
Parameter 184
DAC Cooling Stage-Down Delay 2 minutes
Compressor Minimum Off or Run Times Apply
Page 49
°
°
55
F + 6
Parameter 180 + (Para­
meter 185 X 3)
ON
C4
°
°
55
F + 4
F Diff.
Parameter 180 + (Para­
meter 185 X 2)
ON
C3
OFF
Parameter 180 + (Parameter 185
X 3) - Parameter 182
°
°
OFF
55
F + (2
F X 2) -5
Parameter 180 + ( Parameter
185 X 2) - Parameter 182
°
°
°
F + 2
F - 5
F
5°F Discharge Air Cooling Control
Dead-band (All Stages Same Setting)
Parameter 182
F Diff.
°
°
°
55
F + (2
F X 3) - 5
F
°
F