Lennox Prodigy 2.0 Application Manual page 64

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Object ID
264
274
Space Carbon Dioxide Sensor (Effective)
275
Space Carbon Dioxide Sensor (Local)
276
277
278
Dehumidification Set Point (Effective)
279
281
282
283
285
286
287
288
289
** Multiply the tonnage of the RTU with the value in cubic feet per minute/ton to derive the value in cubic feet minute units.
Table 46. Analog Input Objects List
Object Name
Most Recent Error 10
Space Humidity (Effective)
Space Humidity (Local)
Dehumidification Status
Return Air Temperature
Building Static Pressure
Duct Static Pressure
Exhaust Fan Status
Supply Airflow Status
Blower Motor Speed
Blower Motor Torque
Outdoor Airflow
Units
None
Parts−per−million
Parts−per−million
Percent
Percent
Percent
None
Deg. F
Inches of water
Inches of water
Percent
cubic feet per minute
RPM
Percent
CFM
Page 64
Data Range
1 − 255
0 − 2000
0 − 2000
0 − 100
0 − 100
0 − 100
0 − 2
−8.7 – 164.4
−0.5 − 0.5
0 – 5.00
0 – 100
0 – 480 cfm/ton**
0 – 1500
0 – 100
0–480 cfm/ton**