Lennox Prodigy 2.0 Application Manual page 112

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Control Parameter
No
Screen Name
Parameter Short Description
152
AUTO CHGOVR DEADBND
153
AUTO CHGOVR DELAY
Automatic Changeover Delay
154
OCC BLOWER MODE
155
FREECOOL LOCKOUT SP
Free Cooling Lockout Setpoint
156
FRESH AIR HEAT SP
Fresh Air Heating Setpoint
157
FAH STAGE DEADBAND
Fresh Air Heating Minimum
158
FAH MIN CYCLE TIME
159
FREE COOL SUPPLY SP
Free Cooling Supply Setpoint
Economizer Free Cooling
160
ECON FREECL TEMP SP
Economizer Free Cooling
161
ECON FRCL TMP OFFSET
Economizer Free Cooling
162
ECON FREECL ENTH SP
Economizer Free Cooling
163
ECN FRCL ENTH OFFST
Table 64. M3 Control Parameters
Min.
Automatic Changeover
2.00
Deadband
Check unit parameter
label as default may
1
be altered at factory
Occupied Blower Mode
30.0
40
Fresh Air Heating Stage
3.0
Deadband
2
Cycle Time
45.0
40.0
Temperature Setpoint
00.0
Temperature Offset
10.0
Enthalpy Setpoint
1.0
Enthalpy Offset
Control Value
Default
Max.
Units
Units
3.00
10.00
°F
15
Minutes
test.
AUTO-CYCLES
Option
60.0
°F
30.0
70.0
°F
40.0
10.0
15.0
°F
8
30
Minutes
55.0
65.0
°F
75.0
75.0
°F
10.0
40.0
°F
12.0
19.0
mA
1.0
5.0
mA
Description
Description
Minimum autochangeover dead-band temperature. Dead band
must be greater than or equal to Parameter 142 plus Parameter
143.
Used in room sensor applications.
Autochangeover time delay. Delay between heating and cooling
modes.
Blower control option for room sensor applications during occupied
periods.
Auto Cycle: Blower cycles with demand
On-Continuous 1: blower is on with either the occupancy sensor
or occupancy schedule indicates occupied.
On-Continuous 2: Blower is on only when both the occupancy
sensor and occupancy scheduler indicates occupied.
On-Continuous 3: lower is on only when both the occupancy
sensor and occupancy scheduler indicates occupied. in addition,
blower will be on a minimum of 25% of the time when occupancy
scheduler indicates occupied by the occupancy sensor indicates
not occupied. The 25% minimum is achieved by turning blower on
for 30 minutes and off for 90 minutes.
Locks out free cooling when outdoor temperature is below the set
value.
Setting value to 29°F disables free cooling lockout.
Fresh Air Heating set point. To enable FAH, set this to a value
between 41°F and 70°F.
Fresh Air Heating stage dead-band.
Fresh Air heating minimum cycle time.
Economizer modulates dampers to maintain supply air temperature
(RT6) at this set point during free cooling. DACC reset applies. See
Parameter 207 - Parameter 201
Outdoor Air Temperature is less than parameter setpoint between
41-75°F , or when Outdoor Air temperature is less than Return Air
Temperature between 0-40°F.
Economizer Free Cooling Temperature Offset
Economizer Free Cooling Enthalpy Setpoint
Economizer Free Cooling Enthalpy Offset