Lennox Prodigy 2.0 Application Manual page 89

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Level 2
Level 3
LANGUAGE =
DATE/TIME =
DISPLAY UNITS F/C
MODEL NUMBER =
CONFIGURATION ID 1
CONFIGURATION ID 2
INSTALL
CATALOG NUMBER
SERIAL NUMBER
RTU DESCRIPTION
DEHUMIDIFIER
SENSOR TYPE
NOTE: PARAMETERS AVAILABLE ARE DEPENDENT ON MODEL NUMBER AND CONFIGURATION ID 1 AND 2 SETTINGS
NETWORK =
L-CONNECTION
NETWORK
INTEGRATION
NETWORK = BACNET
Table 58. Menu Interface (Level 1 - SETUP)
Level 4
Level 5
= ENGLISH, ESPANOL, OR FRANCAIS
= DAY, MONTH, YEAR, HOURS, MINUTES, SECONDS
= FAHRENHEIT OR CELSIUS
LOCATED ON UNIT NAMEPLATE.
SEE WHITE STICKER TITLED "ORIGINAL FACTORY UNIT CONFIGURATION" LOCATED ON
THE RIGHT SIDE OF THE CONTROL BOX NEAR THE M3 CONTROLLER.
WHITE STICKER TITLED "ORIGINAL FACTORY UNIT CONFIGURATION" LOCATED ON THE
RIGHT SIDE OF THE CONTROL BOX NEAR THE M3 CONTROLLER.
LOCATED ON UNIT NAMEPLATE
LOCATED ON UNIT NAMEPLATE
= UP TO 18 ALPHA/NUMERIC CHARACTERS
= NONE OR REHEAT DI4
DEHUMIDIFIER DEHUMID SETPOINT = X.XX %
= LOCAL SENSOR OR
NETWORK SENSOR
DEHUMIDIFIER DEHUMID DEADBAND = X.X %
LCONN ADDRESS = X
CONTROL MODE =
ROOM SENSOR, MON­
ITOR ONLY OR NET­
WORK THERMOSTAT
* OCC (OCCUPIED) BLOWER MODE DESCRIPTION:
AUTO CYCLE: BLOWER CYCLES WITH DEMAND
ON-CONTINUOUS 1: BLOWER IS ON WITH EITHER THE OCCUPANCY SENSOR OR OCCU­
PANCY SCHEDULER INDICATES OCCUPIED.
ON-CONTINUOUS 2: BLOWER IS ON ONLY WITH BOTH THE OCCUPANCY SENSOR AND
OCCUPANCY SCHEDULER, BOTH INDICATES OCCUPIED.
ON-CONTINUOUS 3: BLOWER IS ON ONLY WHEN BOTH THE OCCUPANCY SENSOR AND
OCCUPANCY SCHEDULER INDICATES OCCUPIED. IN ADDITION, BLOWER WILL BE ON A
MINIMUM OF 25% OF THE TIME WHEN OCCUPANCY SCHEDULER INDICATES OCCUPIED
BY THE OCCUPANCY SENSOR INDICATES NOT OCCUPIED. THE 25% MINIMUM IS
ACHIEVED BY TURNING BLOWER ON FOR 30 MINUTES AND OFF FOR 90 MINUTES.
BACNET MAC ADDRESS = X
BACNET BAUD RATE = 9.6, 19.2, 38.4 OR 76.8 K
CONTROL MODE =
ROOM SENSOR, MON­
ITOR ONLY OR NET­
WORK THERMOSTAT
Page 90
Level 6
NETWORK SENSOR CO2 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPEATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR ON-
CONTINUOUS 1, 2 OR 3 *
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP
OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
NETWORK SENSOR CO2 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR ON-
CONTINUOUS 1, 2 OR 3 (SEE DESCRIPTION ABOVE)
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP
OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F