Lennox Prodigy 2.0 Application Manual page 106

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Control Parameter
No
Screen Name
Parameter Short Description
Low Ambient Outdoor Air Limit
84
LAC SP TEMP 2
Low Ambient Temperature
85
COMP1 LO TMP LCKOUT
Lockout for Compressor 1
Low Ambient Temperature
86
COMP2 LO TMP LCKOUT
Lockout for Compressor 2
Low Ambient Temperature
87
COMP3 LO TMP LCKOUT
Lockout for Compressor 3
Low Ambient Temperature
88
COMP4 LO TMP LCKOUT
Lockout for Compressor 4
89
COMP MIN OFF DELAY
Compressor Minimum Off Delay
91
COMP MIN RUN TIME
Compressor Minimum Run Time
Maximum High Pressure
98
MAX HP OCCURRENCES
99
MAX LP OCCURRENCES
Low Pressure Switch Ignore
100
LP SW IGNORE TIME
Maximum Stage 1 Cooling Time
101
CL STG 2 STGUP TIME
Before Call for Stage 2 Cooling
Maximum Stage 2 Cooling Time
102
CL STG 3 STGUP TIME
Before Call for Stage 3 Cooling
Table 64. M3 Control Parameters
Min.
10.0
Temperature 2 Setpoint
Check unit parameter
label as default may
-31.0
be altered at factory
Check unit parameter
label as default may
-31.0
be altered at factory
-31.0
-31.0
60
60
1
Occurrences
Maximum Low Pressure
1
Occurrences
0
Time
0
0
Control Value
Default
Max.
Units
Units
55.0
60.0
ºF
80.0
ºF
test.
80.0
ºF
test.
0.0
80.0
ºF
0.0
80.0
ºF
300
510
Seconds
240
510
Seconds
3
8
Occurrences
3
8
Occurrences
120
600
Seconds
912
3600
Seconds
912
3600
Seconds
Description
Description
Low ambient outdoor air limit temp. 2. Parameters 83 and 84 are
used to shed fans.
See Operation section.
Temperature setting must be greater than or equal to Parameter
83.
Low ambient lockout for compressor 1.
A value of (-31°F) will disable low ambient lockout function.
Temperature setting must be less than or equal to Parameter 86.
Low ambient lockout for compressor 2.
A value of (-31F) will disable low ambient lockout function.
Temperature setting must be greater than or equal to Parameter
85 and less than or equal to Parameter 87.
Low ambient lockout for compressor 3.
A value of (-31F) will disable low ambient lockout function.
Temperature setting must be greater than or equal to Parameter
86 and less than or equal to Parameter 88.
Low ambient lockout for compressor 4.
A value of (-31F) will disable low ambient lockout function.
Temperature setting must be greater than or equal to Parameter
87
Compressor minimum off delay.
Compressor minimum run time.
Maximum High Pressure occurrences that are stored before control
locks off compressor stage and energizes the service output.
Maximum Low Pressure occurrences that are stored before control
locks off compressor stage and energizes the service relay.
Low Pressure Switch Ignore Time
Stage 2 stage up timer. The maximum time that cooling stage 1
runs before calling cooling stage 2.
Used in room sensor applications.
Disabled if set to 0.
Stage 3 stage up timer. The maximum time that cooling stage 2
runs before calling cooling stage 3.
Used in room sensor applications.
Disabled if set to 0.