Lennox Prodigy 2.0 Application Manual page 119

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Control Parameter
No
Screen Name
Parameter Short Description
287
ALGORITHMS ENABLED
305
LON HEARTBEAT TIME
306
ZON SNSR CAL OFFSET
Zone Sensor Calibration Offset
313
FAH REHEAT MODE
Table 64. M3 Control Parameters
Min.
Note: Options for Parameter 287 are not accessible via the M3 Unit Controller user interface. Options can be set using the
Lennox UC software. Default set bit is 0x00000300.
Set Bit
0x00000002 Enable Fresh Air Heating (ALGO_FAH)
0x00000004 Enable Fresh Air Cooling (ALGO_FAC)
0x00000008 Enable DACC Return Air Reset (ALGO_DACC_RAT_RESET)
0x00000010 Enable DACC Outdoor Air Reset (ALGO_DACC_OAT_RESET)
0x00000020 Enable DACH Return Air Reset (ALGO_DACH_RAT_RESET)
0x00000040 Enable DACH Outdoor Air Reset (ALGO_DACH_OAT_RESET)
0x00000080 Enable Supply Static Pressure Sensor Alarm (ALGO_LO_STATIC_PRESSURE_ALARM)
0x00000100 Enable Low Outdoor Temp override of DCV/OAC operation (ALGO_LO_OAT_DCV_OAC_OVERRIDE)
0x00000200 Enable High Outdoor Temp override of DCV/OAC operation (ALGO_HI_OAT_DCV_OAC_OVERRIDE)
0x00000800
Algorithms Enabled
Here is an example of the selection options for
Algorithms Enable via the Lennox UC Software.
LonTalk Heartbeat Time
0
-5
Fresh Air Reheat Mode
0
Control Value
Default
Max.
Units
Units
Description
Enable Free Cooling Blower Stage Up
100
3600
Seconds
0
5
°F
0
3
OPTION
Description
Description
This setting is applicable to local temperature sensor only.
0 = Disabled
1 = Allowed, must be occupied.
2 = Allowed, blower must be energized and in occupied mode.
3 = Allow. No conditions apply.