ALARM
ALARM
TYPE
TYPE
CODES
CODES
DISPLAY MESSAGE
ULTRA: SUCTION PRESSURE SENSOR
182
ALARM
ERROR
ULTRA: COMPRESSOR 1 SUMP
183
ALARM
TEMPERATURE SENSOR ERROR
ULTRA: COMPRESSOR 2 SUMP
184
ALARM
TEMPERATURE SENSOR ERROR
185
ALARM
ENGINEERING USE ONLY.
186
ALARM
BLOWER MOTOR FAULT
TABLE 66. PRODIGY 2.0 ALARM CODES
Event Action
Prodigy provides 0-5VDC analog input for the suction pressure sensor. Sensor output is connected to P333, pin 1. valid
suction pressure range is 0 to 300 psig.
If Suction Pressure Sensor is detected on Ultra unit falls below the 30 psig then Prodigy will assume that the Pressure
Sensor sensor is faulty and ignore Pressure Sensor readings. alarm will automatically clear once input is within normal
operating range.
Alarm will occur when an open or short condition is detected. Alarm will also occur when unit controller via the temperature
sensor detects an out of range. Valid range is ­30°F to 150°F. Possible causes are faulty temperature sensor / circuit or
improper installation.
In systems with EBM blower, prodigy shall start monitoring the motor alarm output (normally closed relay contact) ten
seconds after blower command is sent. The M3 unit controller will stop unit operation if fault conditions (relay contact open
­ logic input high) are detected.
Note: Motor alarm is wired in P259­7; shared with VFD alarm and ECM blower rpm input. Alarm will clear when in­range
temperature is detected.