AIR MANAGEMENT

ROOM TEMPERATURE

Function
The CLIMATIC controls the fresh or heat temperature according to the specifyed set point. The controller is programmed to maintain
a temperature as comfortable as possible with the most economic usage of the unit.
Description
The room temperature is maintained between a minimum threshold (the heating set point) and a maximum threshold (the cooling set
point). The dead zone is defi ned between these 2 thresholds.
1. Fix value
For a friendly use, a single room temperature set point is used. This setting is set in the middle of the dead zone. If the thresholds
(2243 ) or (2242) are modifi ed, the set point (2222) is automatically calculated to the average value.
Changeover mode
Ambient temperature (°C)
(2243)
(2242)
Customer set point
(2222)
The cooling and heating thresholds can be specifi ed according to the scheduling and can take different mode for each schedule mode
(Night, Day, Day I, Day II and BMS).
12h/0h
24h/12h
Night mode
Day mode
18.0°C
22.0°C
Day mode
22.0°C
9h
3h
21h
15h
Night mode
DayI mode
Day II mode
18.0°C
20.0°C
DayI mode
20.0°C
22.0°C
6h
18h
• 6 •