Lennox Prodigy 2.0 Application Manual page 14

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Control Parameter
P
Screen Name
146
COOL STAGE3 DIFFER
147
COOL STAGE4 DIFFER
148
HEAT STAGE1 DIFFER
149
HEAT STAGE2 DIFFER
150
HEAT STAGE3 DIFFER
151
HEAT STAGE4 DIFFER
152
AUTO CHGOVR DEADBND
Table 7. Room Sensor Parameter Summary
Short Description
Min.
Cooling Stage 3
0.00
Differential
Cooling Stage 4
0.00
Differential
Heating Stage 1
0.00
Differential
Heating Stage 2
0.00
Differential
Heating Stage 3
0.00
Differential
Heating Stage 4
0.00
Differential
Automatic Changeover
2.00
Deadband
Page 14
Control Value
Default
Max.
Unit
Unit
1.50
3.00
°F
2.00
3.00
°F
0.50
3.00
°F
1.00
3.00
°F
1.50
3.00
°F
2.00
3.00
°F
3.00
10.00
°F
Description
Description
Cooling stage 3 differential. Used only
with room sensor applications.
Differential temperature must be great­
er than or equal to Parameter 145 and
less than or equal to Parameter 147.
Cooling stage 4 differential. Used only
with room sensor applications.
Differential temperature must be great­
er than or equal to Parameter 146.
Heating stage 1 differential. Used only
with room sensor applications.
Differential temperature must be less
than or equal to Parameter 149.
Heating stage 2 differential. Used only
with room sensor applications.
Differential temperature must be great­
er or equal to Parameter 148.
Heating stage 3 differential temperat­
ure. Used only with room sensor ap­
plications.
Differential temperature must be great­
er than or equal to Parameter 149.
Heating stage 4 differential temperat­
ure. Used only with room sensor ap­
plications.
Differential temperature must greater
than or equal to Parameter 150
Minimum autochangeover dead-band
temperature. Dead band must be
greater than or equal to Parameter 142
plus Parameter 143.
Used in room sensor applications.