M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Note: Available menu options are dependent on hardware configuration.
Level 2
Level 3
BLOWER
RTU OPTION
DAMPER
DEHUMIDIFIER
EDIT PARAMETER
Table 60. Menu Interface (Level 1 - SETTINGS)
Level 4
SPEEDS
VFD BYPASS
ECONOMIZER ENTHALPY OFFSET = X MA
ECONOMIZER TEMP ECON TYPE = TEMPERATURE OFFSET OR TEMPERATURE SETPT
ECONOMIZER OAT SETPOINT = XX.X F
FREE COOLING SUPPLY AIR SETPOINT = XX F
OUTDOOR AIRFLOW = XXX CFM
ADVANCE AIRFLOW ALARMS = ENABLED OR DIS­
ABLED (ONLY VISIBLE IF CONFIGURATION ID 1,
POSITION 2 IS SET CORRECTLY).
MIN DAMPER POSITION BLOWER ON HIGH = X.X %
MIN DAMPER POSITION BLOWER ON LOW = X.X %
DEMAND CONTROL VENT DAMPER START OPEN = XXXX.X PPM
DEMAND CONTROL VENT DAMPER FULL OPEN = XXXX.X PPM
DEMAND CONTROL VENT > DAMPER MAX OA CFM = X CFM
(ONLY VISIBLE IF CONFIGURATION ID 1, POSITION 2 IS SET CORRECTLY).
DEMAND CONTROL VENT DAMPER MAX OPENING = XXX.X%
POWER EXHAUST ON BY ECON TRAVEL = XX.X %
FRESH AIR HEATING
ENABLE FAH = YES OR
NO
FRESH AIR COOLING
ENABLE AFC = YES OR
NO
SENSOR TYPE=LOCAL
SENSOR. NETWORK
SENSOR, REHEAT DI4 OR
NONE
ENTER DATA ID=XXX
Page 94
USE THE ADJUST AND SET VALUES AR­
Level 5
ROWS TO SCROLL UP OR DOWN FOR SE­
LECTION OPTIONS.
BLOWER HEAT = XXXX CFM
BLOWER COOLING HIGH = XXXX CFM
BLOWER COOLING LOW = XXXX CFM
BLOWER VENTILATION = XXXX CFM
ON (TARGET XXXX CFM) ADJUST BLOWER RPM - XXXX RPM
A BOX (NON-EP) -
HIGH SPEED = %
HEATING, HIGH
LOW SPEED = %
SPEED AND LOW
ADJUST BLOWER % = XX%
SPEED
ADVANCE AIRFLOW
A BOX AND B BOX
BLOWER CALIBRATION (HEATING, HIGH
OR BIGGER
SPEED,
HEATING, COOLING
LOW SPEED OR VENTILATION = CALIBRA­
HIGH, COOLING
TION
MED, COOLING
DONE OR TURN BLOWER ON.
MED HIGH,
IF TURN BLOWER ON IS SELECTED, BLOWER
COOLING MED
ON
LOW, COOLOW
XXXXX > TURN BLOWER OFF= NO OR YES.
LOW AND
VENTILATION
VFD BYPASS DISENGAGED ENGAGE? = NO OR YES
ADV AIRFLOW ALARMS LO SPLY AIRFLOW ALM
= XX%
ADV AIRFLOW ALARMS LO OD AIRFLOW ALM =
XX%
ADV AIRFLOW ALARMS HI OD AIFLOW ALM =
XX%
ADV AIRFLOW ALARMS ALM TRIGGER PERIOD
= XXXX SEC
FRESH AIR HEATING FAH SETPOINT = XX F
FRESH AIR COOLING AFC SETPOINT = XX F
= NONE OR REHEAT DI4
DEHUMIDIFIER DEHUMID
= LOCAL SENSOR
SETPOINT = XX.X %
OR NETWORK
DEHUMIDIFIER DEHUMID
SENSOR
DEADBAND = X.X %