Control Parameter
No
Screen Name
Parameter Short Description
Advance Airflow No Airflow
236
NO AIRFLOW ALARM EU
237
OUTDOOR AIR TARGET
Advance Airflow Outdoor CFM
238
OUTDOOR CFM CALIB
Advance Airflow Outdoor CFM
239
LO OD CFM ALARM SP
Advance Air Flow High Outdoor
240
HI OD CFM ALARM SP
Advance Airflow Maximum
241
MAX OD CFM DCV SP
Outdoor CFM Damper Control
Advance Air Flow Low Outdoor
243
LO OD CFM ALARM EU
Advance Air Flow High Outdoor
244
HI OD CFM ALARM EU
Advance Airflow Outdoor Air
245
OD DP ERR ALARM EU
Damper Error Alarm Evaluation
Advance Airflow Altitude Set
246
ALTITUDE STPT
Advance Airflow Blower Ramp
247
EP BLR RAMP RATE SP
Display Unit (Fahrenheit or
258
DISPLAY UNITS F/C
Free Cooling Compressor
285
FRCL COMP LCKOUT MD
Table 64. M3 Control Parameters
Min.
0
Alarm Evaluation
Outdoor Air Target
0
-1200
Calibration
15.0
Alarm Set Point
15.0
CFM Alarm Set Point
0
Ventilation Set Point
0
CFM Alarm Evaluation
0
CFM Alarm Evaluation
0
0
Point
10
Rate Set Point
FAHRENHEIT or
Celsius)
0
Lockout Mode
Control Value
Default
Max.
Units
Units
20
300
Count
400
1000
CFM
0
1200
Count
25.0
100.0
%
25.0
100.0
%
0
2400
CFM
1800
3600
Seconds
1800
3600
Seconds
1800
3600
Seconds
650
25000
Feet
10
35
Torque
OPTION
CELSIUS
2
2
OPTION
Description
Description
Applicable to A Box units only.
Applicable to A Box units only.
Applicable to A Box units only.
Applicable to A Box units only.
Applicable to A Box units only.
Applicable to A Box units only.
Applicable to A Box units only.
Applicable to A Box units only.
Applicable to A Box units only.
Applicable to A Box units only.
0 = Disable Free Cooling Low Ambient Compressor Lockout (de­
fault).
1 = Lockout Compressor whenever the outdoor air is suitable re­
gardless of outdoor air temperature.
2 = Enable Free Cooling Low Ambient Compressor Lockout.