19. Sequence of Operation

19.1. Unit Controller Control Modes
Unit Controller can operate in several different control modes. The selection of these control modes will depend upon
several factors:
Unit type - constant air volume with MSAV.
Room application (single-zone, bypass zoning or zoning)
Which device will control rooftop unit staging and unit operation (thermostat / third-party controller or the M3 Unit
Controller)
The desired level of unit heating and cooling staging (2 heat / 2 cool or 4 heat / 4 cool)
19.1.1. Unit Controller In Room Sensor Mode
When in the room sensor mode, the M3 Unit Controller can provide up to four stages of mechanical heating and cooling
operation. Constant volume units in single-zone applications can use this room sensor mode. The room sensor will provide
space temperature information to the M3 Unit Controller. The M3 Unit Controller houses all space temperature set points
and controls all rooftop unit staging and general operation. The M3 Unit Controller also determines unit error codes,
provides diagnostic information and maintains safe operation limits. It is important to note that scheduling and/or set point
control requires the use of a L Connection Network Control Panel.
24VAC
R
RELATIVE HUMIDITY FOR
HUMIDITROL OR SUPERMARKET
REHEAT OPTION
19.1.2. Unit Controller In Thermostat Mode
When in the thermostat mode, the M3 Unit Controller can provide up to two stages of mechanical heating and cooling
operation. Three stage cool operation is possible with special setting described in section 2.1.1.
Constant volume units in either single-zone or bypass zoning applications can use this control mode. To operate correctly, a
Lennox or third-party thermostat or unit control must provide the following wiring connections to the M3 Unit Controller:
1. Ventilation demand
2. Occupied demand
3. Heating demand one
4. Heating demand two
5. Cooling demand one
6. Cooling demand two
In this configuration, either the thermostat or unit control will control the rooftop unit staging and general operation. The M3
Unit Controller functions primarily to determine unit error codes, provide diagnostic information and maintain safe operation
limits.
1
SEE AFTERMARKET CONTROLLER INSTALLATION
INSTRUCTIONS FOR WIRING INFORMATION.
2
FOR HUMIDITROL OR SUPERMARKET REHEAT OPTION.
THERMOSTAT
G
L
C
G W1
W2
Y1
Y2
OCP
O
RH SENSOR
Figure 27. Constant Air Volume Unit in Single-Zone Application
24VAC
COMMON
VENTILATION DEMAND
HEATING DEMAND ONE
1
AFTERMARKET
RTU CONTROLLER
HEATING DEMAND TWO
COOLING DEMAND ONE
COOLING DEMAND TWO
OCCUPIED DEMAND
Figure 28. Constant Air Volume Unit In Single-Zone Application
SENSOR
24VAC
SENSOR
OUTPUTS
IAQ
R
C
AI1
HUM
TMP D01
D02
ROOM SENSOR
24VAC
G
THERMOSTAT
L
W1
OCP O
R
C
G
W2
Y1
Y2
Page 76
SMOKE
INPUTS
HUMIDISTAT
24VAC
DI1
DI4
C
R
C
DI2
R
DI3
R
24VAC
SENSOR
SENSOR
OUTPUTS
SMOKE
IAQ
24VAC
R
C
DI1
AI1
HUM
TMP
D01
D02
R
C
RH SENSOR
INPUTS
HUMIDISTAT
DI2
R
DI3
R
DI4
C