Control Parameter
No
Screen Name
Parameter Short Description
Constant Air Volume with
Bypass Damper Manual Reset
41
BLOWER MANUAL RESET
Value Output Percentage
Air Supply Static Shutdown
42
STATIC SHUTDOWN SP
Static Pressure Lockout
43
STATIC LOCKOUT CNT
Supply Static Sensor (A30) Low
44
STATIC LO ALARM CHK
Alarm Percentage Setpoint
Electric Heat Warm-up Time
58
HT ELEC WARMUP DLAY
Electric Heat Blower On Delay
59
HT ELEC BLR ON DLAY
Electric Heat Blower Off Delay
60
HT ELEC BL OFF DLAY
Electric Heat Maximum Primary
61
HT ELEC MAX LT OCC
Electric Heat Time Delay
62
HT ELEC STAGE DELAY
Electric Heat Maximum Lower
63
HT ELEC STG UP TMR
Stage Run Time in Room
Electric Heat Time Delay for
Lower Stage Termination
64
HT ELEC STG DWN TMR
Gas Time Delay for Economizer
65
HT GAS WARMUP DELAY
Being Closed During Warm-up
Gas Blower On Delay After
66
HT GAS BLR ON DELAY
Gas Blower Off Delay After
67
HT GAS BLR OFF DLAY
Heading Demand Termination
Table 64. M3 Control Parameters
Min.
20.0
Setpoint
0
Setpoint
1
Counter Setpoint
30.0
Electric Heating Parameters
0
Delay for Economizer
0
Setpoint.
0
Setpoint.
1
and Secondary
12
Between Heat Stages
0
Sensor Applications
0
Following Higher Stage
Termination
Gas Heating Parameters
0
8
Heating Demand
80
Control Value
Default
Max.
Units
Units
52.0
100.0
%
w.c.
2
5
3
7
Counts
40.0
100.0
%
3584
8160
Seconds
0
0
Seconds
20
300
Secs
3
15
Counts
12
60
Seconds
912
3600
Seconds
0
3600
Seconds
3584
8160
Seconds
40
60
Seconds
120
300
Seconds
Description
Description
Constant air volume with bypass damper manual reset value output.
This is the output when unit is off.
Supply static shutdown set point. Unit will shutdown for Parameter
110 minutes if duct pressure exceeds this value for 20 seconds.
The number of occurrences before permanent lockout. Counter
resets when M3 resets.
Refer to Parameter 226 to either enable or disable this feature.
Supply
Static
Pressure
Sensor
(A133_P195_6) (TB18_6) alarm threshold.
Blower percent speed before checking sensor after a 20 second
delay.
A value of 30% disables the low threshold or "open" alarm trap.
Warm-up time delay. The time that the economizer is forced closed
during warm-up (first occupied + heat demand)
The time before the blower turns on after a electric heating demand.
The time the blower stays on after the heating demand is lost.
Service output activation. Maximum Primary and Secondary Limit
occurrences stored before service relay is energized.
Note: Heating stage is not locked out.
Time delay between heat stages.
Stage up timer. The maximum time that lower stage runs before
calling next heat stage. Used in room sensor applications.
Disabled if set to 0.
Time delay before a lower stage turns off following a higher stage
termination.
Used in room sensor applications.
Warm-up time delay. The time that the economizer is forced closed
during warm-up (first occupied + heat demand) .
The time before the blower turns on after a heating demand.
The time the blower stays on after the heating demand is terminated.
(A30)
connected
at