Lennox Prodigy 2.0 Application Manual page 109

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Control Parameter
No
Screen Name
Parameter Short Description
Enable Return Air Temperature
113
EN RET AIR TMP LMT
114
COOL RET AIR LIMIT
115
HEAT RET AIR LIMIT
Maximum Phase Monitoring
116
MAX PHASE MON OCC
Demand Control Ventilation
117
DCV MAX DAMPER OPEN
Maximum Damper Open
Demand Control Ventilation
118
DCV DAMP START OPEN
Demand Control Ventilation
119
DCV DAMP FULL OPEN
Maximum Damper Full Open
Demand Control Ventilation
120
DCV HI TMP OV FL CL
Temperature Override Full
Demand Control Ventilation
121
DCV HI TMP OV ST CL
Temperature Override Start
Demand Control Ventilation
122
DCV LO TMP OV FL CL
Temperature Override Full
Demand Control Ventilation
123
DCV LO TMP OV ST CL
Temperature Override Start
131
FREE CL MAX DAMPER
Free Cooling Maximum Damper
132
MIN DAMPER POSITION
Minimum Damper Position
Table 64. M3 Control Parameters
Min.
0
Limit
Cooling Return Air Limit
60.0
Heating Return Air Limit
60.0
1
Occurrence
0
0
Damper Start Open
0
Setpoint
Outdoor Air Control Hi
-31.0
Closed
Outdoor Air Control Hi
-31.0
Closing
Outdoor Air Control Low
-31.0
Closed
Outdoor Air Control Low
-31.0
Closing
0.0
0.0
Control Value
Default
Max.
Units
Units
0
1
Option
65.0
80.0
°F
85.0
100.0
°F
3
15
Occurrences
100
100
%
700
2000
PPM
1200
2000
PPM
105.0
132.0
°F
75.0
132.0
°F
10.0
132.0
°F
40.0
132.0
°F
100.0
100.0
%
0.0
100.0
%
Description
Description
Enables return air temperature limit option.
Return air limits may be used for limiting zone temperatures. Con­
tinuous fan operation recommended.
Return air limit for cooling. If the return air cooling limit is ex­
ceeded, the cooling demands are interrupted.
Parameter 113 must be set to 1 to enable.
Return air limit for heating. If the return air heating limit is ex­
ceeded, the heating demands are interrupted.
Parameter 113 must be set to 1 to enable.
A42 input occurrences before service relay is energized.
(A55_P299_6)
Maximum allowed demand control ventilation damper open position.
Damper "start open" CO
set point for Demand Control Ventila­
2
tion.
Level where fresh air damper begins to open.
Damper "full open" CO
set point for Demand Control Ventilation.
2
Level where fresh air damper is opened to maximum.
High outdoor air temp. where fresh air damper is closed to minimum
position.
High outdoor air temperature where fresh air damper begins to
close.
Low outdoor air temperature where fresh air damper is closed to
minimum position
Low outdoor air temp. where fresh air damper begins to close.
The maximum allowed fresh air damper opening for free cooling.
Minimum fresh air damper position during occupied operation.