M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

NETWORK = RTU
NETWORK
STANDALONE,
INTEGRATION
L-CONNECTION,
BACNET OR LONTALK
Select the appropriate menu option to determine the room sensor back-up mode. The back-up mode is used in the event
that the A2 room sensor fails or is disconnected. The following options are available:
NONE has no back-up mode of control should the A2 room sensor fail.
ROOM SENSOR option is only available if the control mode is set to NETWORK.
RETURN AIR BACKUP will default to return air sensor RT16 (should the A2 room sensor fail). The M3 Unit Controller
will switch over and operate based on the temperature from the return air sensor. RT16 is standard on all units; therefore
M3 Unit Controller Room Sensor System Mode 3 is the recommended backup mode when units are setup in the room
sensor mode.
THERMOSTAT will default to a local thermostat if one is installed (should the A2 room sensor fail). The M3 Unit
Controller will switch over and operate based on the signals from the room thermostat.
NOTE - The RT16 has a lower resolution than the A2 room sensor and should only be used as back-up.
Table 5. Menu Interface (Level 1 - SETUP)
LCONN ADDRESS = X
CONTROL MODE =
ROOM SENSOR,
MONITOR ONLY OR
NETWORK
THERMOSTAT
Page 9
NETWORK SENSOR CO2 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPEATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR ON-
CONTINUOUS 1, 2 OR 3 *
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP
OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F