Lennox Prodigy 2.0 Application Manual page 53

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Control Parameter
No.
Screen Name
206
DACC RAT RS PRP BND
207
DACC RS LIMIT
Table 42. Discharge Air Cooling Parameters Summary
Control Value
Short
Description
Min.
Discharge
Air Control
Cooling Re­
1.0
turn Air Re­
set Propor­
tional Band
Discharge
Air Control
5.0
Cooling Re­
set Limit
Unit
Default
Max.
Unit
10.0
30.0
°F
10.0
20.0
°F
Page 53
Description
Description
Discharge Air Control Cooling return air
reset proportional band.
Also used to reset free cooling set point
(Parameter 159).
Discharge Air Control Cooling total reset
limit. This limits the total DACC reset al­
lowed.
Also used to reset free cooling set point
(Parameter 159).

Hide quick links: