Property
Property ID
Object_Identifier
75
Object_Name
77
Object_Type
79
Out_Of_Service
81
Lennox_Object_
513
Installed
Lennox_Object_
514
Running
Lennox_Object_
515
Run_Time
Lennox_Object_Min_
516
Cycle_Time
Lennox_Object_
517
Cycle_Count
Lennox_Object_Error
518
Lennox_Object_
533
HeatType
Table 49. Lennox Proprietary Objects - Heating (Object ID: 130)
Data type and range
Integer (0-4194302)
character string of 1 character (min.)
to 32 characters (max.)
130
(OBJECT_LNX_HEATING)
TRUE or FALSE
TRUE or FALSE
Integer (0 - 100)
Integer (0 - 4294967295) minutes
Integer (0 - 4294967295) seconds
Integer (0 - 4294967295) cycles
Integer (0 - 255)
Integer: Values are: 1-Gas; 2-Elec­
tric; 3-Heat Pump mode
Access
Description
Numeric code that identifies the object (unique within
Read Only
Lennox BACnet Device).
Identifies the Object and is unique within the BACnet
Read Only
Device.
Read Only
Indicates membership in a particular object type class.
Indicates whether the heating device is in service or
Read Only
not.
Indicates whether the heating device is installed or
Read Only
not. Unless the value of this property is TRUE, all oth­
er properties of the heating object instance are invalid.
Indicates that heating is not running if the value is zero
Read Only
and that heating is running if a value greater than zero
(range: 0, 100 or possible values).
Indicates the time heating has been running. Internally,
the time that heating has been running is stored into
EEPROM once every hour. Therefore, in the event
Read Only
power turns off, the value returned when power turns
back on will be the last stored value. This can result in
a loss of run-time value up to an hour for each power
cycle event.
Indicates the minimum time heating must run in any
given cycle. This prevents short cycles to help protect
Read Only
the compressor (This property does not apply to Elec­
tric Heat Stage components).
Indicates the number of cycles heating has been run­
Read Only
ning.
Reports any error code heating may have en­
Read Only
countered. A value of 0 means no error while any non-
zero value represent an error.
Indicates the source of power used for heating (range:
Read Only
0, 255).
Page 66