System Relative Humidity Options - Lennox Prodigy 2.0 Application Manual

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Control Parameter
No.
Screen Name
188
SRV OUTPT SP RH
189
SRV OUTPT SP TEMP
190
SRV OUTPT DB C02
191
SRV OUTPT DB RH
192
SRV OUTPT DB TEMP
193
SRV OUTPT DELAY

14.2. System Relative Humidity Options

Option
Description
0 - Hysteresis
1 - Window
NOTE: Fixed 3% relative humidity hysteresis on options 1 - 3
2 - Delayed ON
3 - Delayed OFF
14.3. System Indoor Air Quality / Carbon Dioxide Options
Option
Description
0 - Hysteresis
1 - Window
2 - Delayed ON
3 - Delayed OFF
14.4. System Outdoor Air Temperature Operation
Option
Description
0 - Hysteresis
1 - Window
2 - Delayed ON
3 - Delayed OFF
Table 55. Service Relay Options
Min.
Service Output
Set Point for
Relative Humidity
Service Output
Set Point
-31.0
Temperature
Service Output
Deadband for
Carbon Dioxide
Service Output
Deadband for Rel­
ative Humidity
Service Output
Deadband for
Temperature
Service Output
Delay
ON when relative humidity is equal to or greater than Parameter 188 setting.
OFF when relative humidity is less than Parameter 188 setting minus Parameter 191.
ON when relative humidity is within range.
Parameter 188 plus Parameter 191
Only ON when relative humidity is greater than Parameter 188. Otherwise service delay will be OFF.
When relative humidity falls below Parameter 188 the service delay is turned OFF once Parameter 193 setting (seconds)
is reached.
ON when indoor air quality/carbon dioxide is greater than Parameter 187 setting.
OFF when indoor air quality/carbon dioxide is less than Parameter 187 minus Parameter 190 setting.
ON when indoor air quality/CO2 within range.
Parameter 187 (SRV OUTPT SP CO2) plus Parameter 190 .
ON when indoor air quality/CO2 is greater than Parameter 187. Otherwise service delay will be OFF.
When indoor air quality/CO2 falls below Parameter 187 the service delay is turned OFF once Parameter 193 setting
(seconds) is reached.
ON when outdoor air temperature is greater Parameter 189 setting.
OFF when outdoor air temperature is less than Parameter 189 setting.
ON when outdoor air temperature is within range.
Parameter 189 plus Parameter 192.
ON when outdoor air temperature is greater than Parameter 189 setting. Otherwise service delay will be OFF.
When outdoor air temperature falls below Parameter 189 the service delay is turned off once Parameter 193 setting
(seconds) is reached.
Control Value
Default
Max.
Unit
Unit
0
100
100
%
51.0
132.0
°F
16
102
2000
ppm
2.0
13.0
100.0
%
1.0
8.0
162.0
°F
64
416
8160
Sec
Page 70
Description
Description
Service Output Set Point for Relative Humidity
Service Output Set Point Temperature
Service Output Deadband for Carbon Dioxide
Service Output Deadband for Relative Humidity
Service Output Deadband for Temperature
Service Output Delay