Lennox Prodigy 2.0 Application Manual page 115

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Control Parameter
No
Screen Name
Parameter Short Description
186
SRV OUTPT CTRL MODE
Service Output Control Mode
Service Output Setpoint for
187
SRV OUTPT SP C02
Service Output Set Point for
188
SRV OUTPT SP RH
Service Output Set Point
189
SRV OUTPT SP TEMP
Service Output Deadband for
190
SRV OUTPT DB C02
Service Output Deadband for
191
SRV OUTPT DB RH
Table 64. M3 Control Parameters
Control Value
Min.
0
0
Carbon Dioxide
0.0
Relative Humidity
-31.0
Temperature
16
Carbon Dioxide
2.0
Relative Humidity
Default
Max.
Units
Units
0
127
Option
996
2000
ppm
100.0
100.0
%
51.0
132.0
°F
102
2000
ppm
13.0
100.0
%
Description
Description
A55 Service Output Control Mode = X + 32*Y + 16*Z
Input source = X:
0-
None. Standard Service Output based on alarms.
1-
Compressor 1 duty cycle. (Compressor crankcase heater functio
On when Outdoor Air Temperature is less than or equal to Pa
meter 189 and greater than or equal to Parameter 192 secon
have passed with compressor 1 off.
Off when Outdoor Air temperature is greater than Parameter 1
plus 3°F (fixed dead-band) or is less than Parameter 1
seconds have passed with compressor 1 off
2-
On when occupied.
3-
On when blower on,
4-
On when heating demand.
5-
On when cooling demand.
6-
On when heating or cooling demand.
7-
System Relative Humidity (A55_P298_5 RH)
8-
System Indoor Air Quality. (A55_P298_3 IAQ)
9-
System Outdoor Air Temperature (A55_P267_1/2 OAT)
10- Energy Recovery System
11- SCR Option for Electric Heat
Algorithm Y for input sources 7-9:
0-
Hysteresis loop (see sections 14.2 - 14.4)
1-
Window - On when input is in range; (see sections 14.2 - 14.4)
2-
Delayed-on. (see sections 14.2 - 14.4)
3-
Delayed-off. (see sections 14.2 - 14.4)
Inversion Z:
0-
Output not inverted.
1-
Output inverted.
A55 service relay output set point.
Service Output Set Point for Relative Humidity
Service Output Set Point Temperature
A55 service relay output dead-band or delay.
Service Output Deadband for Relative Humidity