Control Parameter
No
Screen Name
Parameter Short Description
164
ECONOMIZER PROFILE
165
FAH STAGE DIFFER
Fresh Air Heating Control
166
FAH REHEAT OAT SP
Fresh Air Heating Control
167
FAH REHEAT DAMPER
Reheat Damper Position
168
FAH REHEAT SP
Fresh Air Heat Control Setpoint
Fresh Air Tempering Automatic
169
FAT AUTO CHGOVR DLY
170
FRESH AIR COOL SP
Fresh Air Cooling Setpoint
Fresh Air Cooling Control
171
FAC STAGE DEADBAND
Table 64. M3 Control Parameters
Min.
Economizer Profile
0
Fresh Air Heating Stage
0.0
Differential
Reheat Outdoor Air
20.0
Temperature Setpoint
5.0
40.0
896
Changeover Delay
60.0
3.0
Deadband
Control Value
Default
Max.
Units
Units
2
3
Option
System 2 Parameters
2.0
20.0
°F
45.0
60.0
°F
40.0
100.0
%
40.0
70.0
°F
1792
7200
Seconds
90.0
90.0
°F
10.0
15.0
°F
Description
Description
These are the operating profile options for the economizer damper
during free cooling when any compressor is on and can be selected
as follows:
Option 0: Damper continues to modulate while compressors are on,
but the effect of mechanical cooling may force the damper closed to
its minimum position. After compressor starts, the free cooling set­
point is lowered to a fixed temperature of 45°F.
Option 1: Damper opens to its max­open position (Parameter 131 -
FREE CL MAX DAMPER) when any compressors start.
NOTE - When using Option 1 and after the compressor is stopped,
the M3 shall resume damper modulation.
Option 2: Damper continues to modulate while compressors are on,
but the effect of mechanical cooling may force the damper closed to
its minimum position. This is the factory default setting.
Holds­off compressor on Y2 call until damper has modulated to
maximum position (Parameter 131 - FREE CL MAX DAMPER)
for three minutes.
After three minutes, compressor starts and the free cooling set­
point is lowered to 45°F. Damper is not locked at maximum open
while compressor is on, but modulates to maintain 45°F discharge
air temperature.
When Y2 is satisfied, compressor goes off and free cooling set­
point is restored to 55°F (Parameter 159 - FREE COOL SUPPLY
SP).
Option 3: Same as Option 2, but with a 10 minute delay instead of a
three minute delay.
Fresh Air Heating stage differential.
0 value for first stage heating only for Fresh Air Heating.
Outdoor air temperature set point that enables fresh air heating for
reheat demand and opens damper to Parameter 167 when outdoor
air is less than set point.
Fresh air damper position during Fresh Air Heating reheat operation.
Fresh Air Heating Reheat set point.
Fresh Air Heating Control or Fresh Air Cooling Control air Tempering
auto-changeover delay.
Fresh Air Cooling set point.
To enable Fresh Air Cooling Control, set this to a value between
60°F and 90°F.
Fresh Air Cooling stage dead-band.