Electric Heat Operation-Electric / Electric Units; Electric Heat Operation; Primary Or Secondary Limits; Sensors - Lennox Prodigy 2.0 Application Manual

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

3.5.
Electric Heat Operation—Electric / Electric Units
3.5.1.
Electric Heat Stage Delay Operation
First-stage heating demand energizes first-stage electric heat (K15 and K17). Second-stage heating demand energizes
second-stage electric heat (K16 and K18). When first-stage and second-stage heating demands are simultaneous, a delay
will occur between stage one and two (Parameter 62). Default delay is 12 seconds. Optional range setting is 12 to 60
seconds.
Go to SETTINGS > RTU OPTION > EDIT PARAMETER = 62 (HT ELEC STAGE DELAY)
3.5.2.

Primary or Secondary Limits

If an electric heat limit (S15 or S63) opens, electric heat is de-energized.
If an electric heat limit opens three times (default) during a thermostat cycle, in addition, the service alarm output will
turn on. Valid options for Parameter 61 are 1 through 15.
Go to SETTINGS > RTU OPTION > EDIT PARAMETER = 61 (HT ELEC MAX LT OCC)

4. Sensors

The M3 Unit Controller is only compatible with L-Connection sensors provided with the unit or purchased separately as
specified in the Product Specification.
All 0-10VDC sensors require two separate twisted pair cables with shield. One cable is used for the 24VAC power and
one cable is used for the 0-10VDC output. Room sensors require a single twisted pair cable with shield. The shield drain
wires must be connected to the common at the unit field wiring terminal block only. The shield drain wires must not be
connected to common at the sensor. Non-communicating temperature sensors require single twisted pair wire only.
4.1.

Temperature Sensors - Provided With Unit

The return air (RT16) and discharge air (RT6) duct probes and the outdoor air (RT17) are all two wire thermistors. The
resistance vs. temperature table is shown below:
Temp. °F (°C)
Resistance +/-2%
-40 (-40)
-20 (-28.9)
0 (-17.8)
20 (-6.7)
30 (-1.1)
4.2.

Optional Room Sensor

Room sensor (A2) is a two-wire thermistor with 1k series resistor.
Temp. °F (°C)
Resistance +/-2%
40 (4.4)
45 (7.2)
50 (10)
55 (12.8)
4.3.

Optional Relative Humidity Sensor

The indoor relative humidity sensor (A91) is an analog sensor with a 0-10VDC output over a relative humidity range of
0-100% relative humidity. The sensor is powered with 24VAC.
4.4.

Optional Carbon Dioxide (Indoor Air Quality) Sensor

The indoor carbon dioxide sensor (A63) is an analog sensor with a 0-10VDC output over a carbon dioxide range of 0-2000
ppm as shown in the following table. The sensor is powered with 24VAC.
Carbon Dioxide
DC Voltage
PPM
0
0
200
1
400
2
Temperature °F
(°C)
335,671
40 (4.4)
164,959
50 (10)
85,323
60 (15.6)
46,218
70 (21.1)
34,566
80 (26.7)
Temperature °F
(°C)
27,102
60 (15.6)
23,764
65 (18.3)
20,898
70 (21.1)
18,433
75 (23.9)
Carbon
DC Voltage
Dioxide PPM
600
800
1000
IMPORTANT
Resistance +/-2%
26,106
19,904
15,313
11,884
9,298
Resistance +/-2%
16,313
14,474
12,882
11,498
Carbon
Dioxide PPM
3
1200
4
1400
5
1600
Page 22
Temp. °F (°C)
Resistance +/-2%
90 (32.2)
100 (37.8)
120 (48.9)
130 (54.4)
Temp. °F (°C)
Resistance +/-2%
80 (26.7)
85 (29.4)
90 (32.2)
DC Voltage
Carbon
Dioxide PPM
6
1800
7
2000
8
7,332
5,826
3,756
3,047
10,299
9,249
7,529
DC Voltage
9
10