Lennox Prodigy 2.0 Application Manual page 48

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

9.4.2.5.
Tuning
In the event that the PID loop requires tuning, the following two methods are recommended depending on the severity of the
problem:
1. In most cases the parameters will only need a small adjustment. In that case use the following table as a basic guide.
Change Desired
Reduce Response time
Reduce Overshoot
Reduce Settling Time
Reduce Offset (steady state error)
2. If method 1 adjustment does not stabilize the system, you may use the following tuning method:
NOTE ­ To use this method the system must be allowed to operate at the manual reset value (% output) without damaging
the system.
A
Set the Parameters 31, 32 and 33 blower PID constants to 0 (OFF).
B
Start system. Analog output value will be at the Parameter 41 (BLOWER MANUAL RESET) value (%).
C
Monitor system. System should be stable. If system is not stable at this point check for other problems. Adjusting
the PID parameters will not solve this problem.
D
If system is stable, gradually increase the Parameter 31 (BLOWER PID P CONST) until system starts oscillating
(moving above and below set point, continuously).
E
Reduce the Parameter 31 (BLOWER PID P CONST) to 40­70% of the value set in step D.
F
Gradually start adding some Parameter 32 (BLOWER PID I CONST) by setting to 127 and reduce setting until the
steady state error (offset) is reduced to an acceptable level.
G If necessary, increase the Parameter 33 (BLOWR PID D CONST) to reduce overshoot. Use of Parameter 33 (D)
can increase settling time and/or lead to instability.
NOTE ­ In most cases, it is best to not use any Parameter 33 (BLOWR PID D CONST).
Table 41. Tuning
Parameter 31
PID P
Increase
Decrease
­
Increase
Page 48
Parameter 32
PID I
Decrease
Increase
Decrease
Decrease
Parameter 33
PID D
Decrease
Increase
Decrease
­

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents