Lennox Prodigy 2.0 Application Manual page 116

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Control Parameter
No
Screen Name
Parameter Short Description
Service Output Deadband for
192
SRV OUTPT DB TEMP
193
SRV OUTPT DELAY
Number of compressors to shed
194
LOAD SHED NUM COMP
196
MAC ADDRESS
197
BAUD RATE
Discharge Air Control Cooling
Outdoor Air Temperature
201
DACC OAT RS ADJ BND
Discharge Air Control Cooling
Outdoor Air Temperature
202
DACC OAT RS ADJ SP
Discharge Air Control Cooling
203
DACC OAT RS PRP BND
Discharge Air Control Cooling
Return Air Reset Adjustment
204
DACC RAT RS ADJ BND
Discharge Air Control Return Air
205
DACC RAT RS ADJ SP
Reset Adjustment Set Point
Discharge Air Control Cooling
206
DACC RAT RS PRP BND
Return Air Reset Proportional
Discharge Air Control Cooling
207
DACC RS LIMIT
Discharge Air Control Heating
208
DACH OAT RS ADJ BND
Outdoor Air Temperature
Resent Adjustment Band
Discharge Air Control Heating
209
DACH OAT RS ADJ SP
Reset Adjustment Set Point
Table 64. M3 Control Parameters
Min.
1.0
Temperature
Service Output Delay
64
0
during load shedding
MAC Address
0
Baud Rate
0.0
Adjustment Band
40.0
Cooling Reset Set Point
Outdoor Ambient Air
1.0
Temperature Cooling
Proportional Band
0.0
Band
50.0
1.0
Band
5.0
Reset Limit
0.0
-31.0
Control Value
Default
Max.
Units
Units
8.0
162.0
°F
416
8160
Seconds
0
15
Option
128
128
Address
9.6K
19.2K
Option
38.4K
76.8K
System 3 Parameters
0.0
30.0
°F
80.0
100.0
°F
20.0
60.0
°F
0.0
30.0
°F
70.0
80.0
°F
10.0
30.0
°F
10.0
20.0
°F
0.0
30.0
°F
40.0
60.0
°F
Description
Description
Service Output Deadband for Temperature
Service Output Delay
Number of compressors to be turned off when load shedding is act­
ive.
BACnet MAC Address. A value of 0-127 sets the BACnet MAC ad­
dress to that value.
Baud rate setting.
Discharge Air Control Cooling outdoor temperature ambient cool­
ing adjustment reset band.
Also used to reset free cooling set point (Parameter 159).
Discharge Air Control Cooling outdoor air temperature cooling re­
set set point.
Also used to reset free cooling set point (Parameter 159).
Discharge Air Control Cooling outdoor ambient temperature cool­
ing proportional band.
Also used to reset free cooling set point (Parameter 159).
Discharge Air Control Cooling return air reset adjustment band.
0 disables return air cooling reset.
Also used to reset free cooling set point (Parameter 159).
Discharge Air Control Cooling return air reset set point.
Also used to reset free cooling set point (Parameter 159).
Discharge Air Control Cooling return air reset proportional band.
Also used to reset free cooling set point (Parameter 159).
Discharge Air Control Cooling total reset limit. This limits the total
DACC reset allowed.
Also used to reset free cooling set point (Parameter 159).
Discharge Air Control Heating outdoor temperature reset adjust­
ment band.
Discharge Air Control Heating outdoor temperature reset set point.