Lennox Prodigy 2.0 Application Manual page 102

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

Control Parameter
No
Screen Name
Parameter Short Description
2
LANGUAGE
Variable Air Volume Control
5
VAV CONTROL MODE
6
BLOWER SMOKE OUTPUT
7
BLOWER HEAT OUTPUT
8
BLOWER COOL OUPUT
Minimum Damper Position
During High Speed Blower
9
MIN DAMPER LOW BLWR
Free Cooling Blower Stage Up
10
FREE CL STG UP DLY
11
ENBL FIELD STAT RPT
Enabled Field Status Report
Multi-Stage Air Volume Smoke
12
MSAV SMK CFM
Maximum Cubic Feet Per
19
MAX CFM RPM
Minute Revolutions Per Minute
Minimum Output Cooling Vent
27
MIN OUPT CL VT SMK
Smoke Detection Mode (Alarm)
28
MIN OUTPUT HEAT
29
MIN DAMPER BLOWER
Minimum Damper Blower
30
PWREXH STG2 MIN BLR
Table 64. M3 Control Parameters
Min.
= ENGLISH, ESPA
LANGUAGE
(SPANISH) or FRAN
Power and Damper Parameters
specific unit, see unit
0
Mode
parameter label for
Blower Smoke Output
20.0
Default settings are
listed in section 9.
Blower Heat Output
20.0
Check unit label as
parameters may be
configured to order.
Blower Cool Output
20.0
0.0
Operation
0
Delay
Check unit parameter
label as default may
450
Detection Mode (Alarm)
be altered at factory
Check unit parameter
label as default may
445
be altered at factory
30.0
Minimum Output Heat
30.0
Check unit parameter
label as default may
0.0
be altered at factory
Power Exhaust Stage 2
0.0
Minimum Blower
Control Value
Default
Max.
Units
Option
(FRENCH)
If applicable to
255
Option
default setting
100.0
%
100.0
%
100.0
%
0.0
100.0
%
300
1800
Sec
0 = OFF
Option
1 = ON
14400
CFM
test.
1780
RPM
test.
50.0
100.0
%
50.0
100.0
%
101.0
%
test.
70.0
100.0
%
Description
Select desired language for user interface. Options are English,
French and Spanish.
Applicable to A Box units only.
16 - Runs the blower in high speed when occupied and there is not
other active demand (room sensor mode only)
32 - Runs the blower in high speed when G is active and there is no
other active demand (thermostat mode only)
Applicable to A Box units only.
Blower staged percentage output during smoke detection.
Applicable to A Box only.
Blower staged percentage output high speed; used for heating and
high cooling or ventilation.
Applicable to A Box units only.
Blower staged percentage output low speed; used for low cooling or
ventilation.
Minimum damper position during low speed blower operation.
Use Parameter 132 during high speed blower operation
Applicable to A Box units only.
Free cooling blower stage-up delay. Blower runs low speed during
delay, and then shifts to high speed.
Enabled Field Status Report
Multi-Stage Air Volume Smoke Detection Mode (Alarm)
NOTE: In order for the SMOKE CFM change to take affect, go the
SETUP > TEST & BALANCE > BLOWER and run the the wizard.
Performing this task will recalculate the output to the desired CFM.
No adjustments are required during this procedure.
Maximum Cubic Feet Per Minute Revolutions Per Minute
Minimum Output Cooling Vent Smoke Detection Mode (Alarm)
Minimum Output Heat
Setting this parameter to 101.0% will disable this feature.
Power Exhaust Stage 2 Minimum Blower