Analog Output Objects - Lennox Prodigy 2.0 Application Manual

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

(not termin­
ated)
(terminated)
The configuration shown above has terminations on the
M3 Unit Controller BACnet modules at both ends and
ONLY at both ends of the chain.
The configuration shown to the right has a termination at
the controller/router on one end and a termination at the
M3 Unit Controller BACnet module on the other end; ter­
minations are ONLY at the ends of the chain.
Cable type - twisted pair with shield, 22 awg minimum,
Belden #88761 or #8761 (Lennox 27M19, 94L63, 68M35).

12.4. Analog Output Objects

Optional Properties Supported:
Optional Writable Properties:
Analog output object's Overridden status flag set if the equivalent set point in the M3 Unit Controller is written to by an Sbus
device.
Object ID
Object Name
101
Application Mode Control
102
Outdoor Air Min PPS Control
103
Occupancy Override Control
104
Occupancy Scheduler Control
107
Occupancy Sensor Input
108
Space Dehumidification Set point
109
Temperature Set Point (abs)
110
Temperature Set Point Offset
113
Space Temperature Input
114
Emergency Override Control
115
Compressor Enable Control
117
Primary Heat Enable Control
119
Auxiliary Heat Enable Control
123
Duct Static Set Point
124
Building Static Set Point
125
Discharge Air Cooling Set Point
126
Discharge Air Heating Set Point
127
Supply Fan Capacity Input
128
Exhaust Fan Capacity Input
129
Set Economizer Outdoor Air Suitable
CONTROLLER/
ROUTER
(not terminated)
(not terminated)
CONTROLLER/
(terminated per mfg
Figure 21. Terminating ends of daisy-chained networks
Min_Pres_Value, Max_Pres_Value
Out_Of_Service
Table 44. Analog Output Objects List
Units
None
Percent
None
None
None
Percent
Deg. F
Deg. F
Deg. F
None
None
None
None
In. of water
In. of water
Deg. F
Deg. F
Percent
Percent
None
(not terminated)
ROUTER
(not terminated)
instructions)
Min. Value
Max. Value
0
255
0
255
0
255
0
255
0
255
0
100
36.25
100
-32
31.75
36.25
100
0
255
0
255
0
255
0
255
0
5
-0.5
0.5
40
80
60
140
101
255
101
255
0
255
Page 61
(not ter­
minated)
(terminated)
(not ter­
minated)
(terminated)
Valid Values within Range
0,1,3,6,9,208,209,216,217,218,224‐254,255*
If set to 101 through 255, local M3 Unit
Controller parameter will be used.
-9,40‐80*
-9,80‐140*
If set to 101 through 255, local M3 Unit
Controller parameter will be used.