When a client connection is configured as the user communication client, the SmartAXIS communicates with the specified server
device according to the settings configured in the ETXD and ERXD instructions that are programmed for the client connection. The
remote host number and other communication settings can be configured in the Connection Settings tab in the Function Area
Settings dialog box.
Specifications (User Communication Client)
Item
Remote host number
Establish connection
Disconnect connection
Number of remote hosts that the SmartAXIS
can communicate simultaneously
Receive timeout
Note 1: Can be enabled or disabled in Function Area Settings, Connection Settings.
Note 2: The settings can be configured in the Connection Settings tab in the Function Area Settings dialog box.
Note 3: The receive timeout is enabled when using the ERXD instruction. To disable the receive timeout, set it to 25500 ms.
Establishing/Disconnecting User Communication Client Connections
When user communication clients are configured, connections are established on TCP/IP protocol. The connections are established
when ETXD/ERXD instructions are executed or when the SmartAXIS has started to run (See Note 1 above). After a connection has
been established, the connection will be kept open until either the SmartAXIS is stopped or a special internal relay allocated to the
connection is turned on.
Device Address
M8130
M8131
M8132
User Communication Client Receive Instruction (ERXD) Cancel Flag
The allocation of the user communication receive instruction cancel flags for each client connection is shown in the table below.
For details about the user communication receive instruction cancel flag, see Chapter 25 "User Communication Instructions" in the
SmartAXIS Ladder Programming Manual.
Device Address
M8100
M8101
M8102
10-16
I
NSTRUCTIONS
1 to 255
When ETXD/ERXD Instructions are executed
When the SmartAXIS starts to run (Note 1)
When the SmartAXIS is stopped
When special internal relays (M8130 to M8132) are turned on
One remote host per a user communication client (Note 2)
100 to 25400 ms (100 ms increments); Default: 1000 ms (Note 3)
Description
Connection 1 Disconnect
Connection 2 Disconnect
Connection 3 Disconnect
User Communication Receive Instruction Cancel Flag (Connection 1)
User Communication Receive Instruction Cancel Flag (Connection 2)
User Communication Receive Instruction Cancel Flag (Connection 3)
S
AXIS P
/L
MART
RO
User Communication Client
When the reply is turned on, the corresponding
connection is disconnected.
Description
U
'
M
FT9Y-B1378
ITE
SER
S
ANUAL
Operation