Troubleshooting Diagram 7
Cannot stop or reset operation.
Is stop or
reset input designated in
the WindLDR Function Area
Settings?
Is the designated stop or
reset input on?
Monitor the designated stop or reset
input using WindLDR on a computer.
Does the monitored input
turn on and off?
Call IDEC for assistance.
NO
YES
NO
YES
NO
YES
S
AXIS P
MART
Note: To monitor M8000, from the WindLDR menu bar, select
Online > Monitor > Monitor, then Online > Custom > New
Custom Monitor. Enter M8000 in the Device box in the Custom
Monitor dialog box.
Turn on the designated input.
The input circuit in the SmartAXIS is
damaged.
Replace the SmartAXIS.
Note: To turn off M8000, enter 0 in the Current Value box in the
Custom Monitor dialog box.
/L
U
'
M
FT9Y-B1378
RO
ITE
SER
S
ANUAL
14: T
ROUBLESHOOTING
Monitor the start control special internal
relay M8000 using WindLDR on a
computer.
YES
Is M8000 off?
NO
Turn off the start control special internal
relay M8000 using WindLDR on a
computer.
14-15