User Communication Cable 1C (FC2A-KP1C)
Cable Length: 2.5m (8.2 feet)
3
6
1
4
7
2
5
8
Mini DIN Connector Pinouts
Pin
Signal line (RS232C)
1
RTS
Request to Send
2
DTR
Data Terminal Ready
3
TXD
Transmit Data
4
RXD
Receive Data
5
DSR
Data Set Ready
6
SG
Signal Ground
7
SG
Signal Ground
8
NC
No Connection
Cover
Caution
O/I Communication Cable (HG9Z-XC295)
Cable Length: 5m (16.4 feet)
To SmartAXIS
D-sub 9-pin Female Connector Pinouts
Description
RS
ER
SD
RD
DR
SG
SG
NC
Shield
B
A
NC
NC
NC
NC
SG
NC
Do not connect any wiring to NC terminals, otherwise operation failure or device damage may be caused.
Pin
1
2
3
4
5
6
7
8
Cover
S
AXIS P
MART
Signal line (RS485)
No Connection
No Connection
No Connection
No Connection
Signal Ground
No Connection
/L
U
'
M
FT9Y-B1378
RO
ITE
SER
S
ANUAL
AWG#
Color
28
Black
Twisted
28
Yellow
28
Blue
28
Green
28
Brown
28
Gray
26
Red
Twisted
26
White
Shield
To HG2G-5F, 3G/4G
Mini DIN Connector Pinouts
Pin
Description
2
RD
3
SD
5
SG
7
RS
8
CS
Cover
Shield
A
PPENDIX
Signal Direction
A-9