You can run and stop the user program, monitor device values, and modify settings on the SmartAXIS Pro by using the LCD and
operation buttons on the SmartAXIS. This chapter describes how to modify the user program and device values with the operation
buttons.
Function Description
The following functions can be used with SmartAXIS button operations.
Type
Run/stop
Switching run/stop
operation
Confirming/Clearing changed timer/
Edit Program
counter preset values
Environment
settings
Configurations
Calendar/Clock
Device Monitor
Program Monitor
Monitors
Status Monitor
Error Monitor
Message display
Message display
Uploading user program
Memory Cartridge
Downloading user program
Stop Access
SD memory card
Format
Initial Screen
The screen below is displayed when the SmartAXIS is purchased and first turned on.
The default menu language is English. To switch the menu language to Japanese, see "Changing the Menu Language" on page 6-
8.
UNCTION
Function
Slave Number/
Message Scroll/Blink
Menu Language/
LCD backlight ON time
Power turned on
Standard screen
Stopped
2000/JAN/01/SAT
00:00:00
S
AXIS P
MART
The program running state (run/stop) can be changed with the
operation buttons on the SmartAXIS.
Change timer/counter preset values or writes them to the user
program in the ROM.
Some of the function area settings (slave number, message scroll
speed, scroll unit, blinking speed, and LCD backlight ON time) can be
modified.
The system menu language can also be changed.
Configures the calendar/clock of the SmartAXIS internal clock.
Displays/modifies the specified device values.
Displays the ladder program.
The on/off state of bit devices can be changed. This is only enabled
when ladder program is selected as the programming language.
Displays the system software version, operating status, scan time, and
protection status.
Enables you to check errors that have occurred on the SmartAXIS.
Displays messages with pre-configured formats on the SmartAXIS LCD
using the MSG instruction/FB.
The user program in the SmartAXIS can be transferred to the memory
cartridge.
The user program on the memory cartridge can be transferred to the
SmartAXIS.
Stops the access to the SD memory card in order to remove the SD
memory card from the SmartAXIS.