Troubleshooting Diagram 2
SmartAXIS Lite - The Power/Run Status LED (PWR/RUN) is not On
The SmartAXIS Lite power/run status LED (PWR/RUN) is on while running and flashes while stopped.
status LED is not on.
Is the error status LED on?
Click the Start button in WindLDR on a
computer connected to the SmartAXIS.
run status LED on?
Monitor M8000 (start control special
internal relay) using WindLDR.
YES
Turn on M8000 using WindLDR.
run status LED on?
14-10
The power/run
NO
Is the power/
NO
Is M8000 on?
NO
YES
Is the power/
NO
S
AXIS P
MART
YES
See Troubleshooting Diagram 3,
"SmartAXIS Lite - The Error Status LED (ERR) is On"
Note: The Start button is found in the WindLDR menu bar.
YES
Note: To monitor M8000, from the WindLDR menu bar, select Online >
Monitor > Monitor, then Online > Custom > New Custom Monitor. Enter
M8000 in the Device box in the Custom Monitor dialog box.
Note: To turn on M8000, enter 1 in the Current Value box in the
Custom Monitor dialog box.
NO
/L
U
'
M
FT9Y-B1378
RO
ITE
SER
S
ANUAL
Is stop or reset input
designated using Function Area
Settings?
YES
Turn off the stop and reset inputs.
Is the power/
run status LED on?
NO
Call IDEC for assistance.
YES
END