IDEC FT1A Series User Manual page 24

Hide thumbs Also See for FT1A Series:
Table of Contents

Advertisement

2: P
S
RODUCT
PECIFICATIONS
General Specifications
AC Power Type
Type Number
Normal Operating Conditions
Operating Temperature
Storage Temperature
Relative Humidity
Pollution Degree
Degree of Protection
Corrosion Immunity
Altitude
Installation Location
Device Class
Overvoltage Category
Vibration Resistance
Shock Resistance
Power Supply (Note 3)
Rated Power Voltage
Allowable Voltage Range
Rated Power Frequency
Maximum Power Consumption
Allowable Momentary Power Interruption
Dielectric Strength Voltage
EMC Immunity
Inrush Current
Ground
Grounding Wire
Power Supply Wire
Effect of Improper Power Supply
Connection
Weight
Note 1: Use in environments that satisfy product specifications.
Note 2: UL, c-UL Listed at 0 to +50°C (FT1A Version V110).
Note 3: Supports input/output overvoltage protection. When overvoltage protection occurred, the power supply output is shut off. In this situation,
shut off the AC input, wait for one minute or longer, and then turn on the AC input again.
2-4
H12RC, B12RC
0 to +55°C (operating ambient temperature) (Note 2)
–25 to +70°C (no freezing)
10 to 95% (non-condensing, operating and storage humidity)
2 (IEC60664-1)
IP20 (IEC60529)
Atmosphere free from corrosive gases
Operation: 0 to 2,000m (0 to 6,565 feet)
Transport: 0 to 3,000m (0 to 9,840 feet)
Inside cabinet (Note 1)
Open equipment
II
When mounted on a DIN rail or panel surface:
5 to 8.4Hz amplitude 3.5mm, 8.4 to 150Hz acceleration 9.8m/s
2 hours per axis on each of three mutually perpendicular axes
2
147 m/s
(15G), 11ms duration, 3 shocks per axis on three mutually perpendicular axes
100 to 240V AC
85 to 264V AC
50/60Hz (47 to 63Hz)
18VA
10ms maximum (at the rated power voltage)
Between power and PE terminals: 1,500V AC, 1 minute
Between input and PE terminals: 1,500V AC, 1 minute
Between transistor output and PE terminals: 1,500V AC, 1 minute
Between relay output and PE terminals: 2,300V AC, 1 minute
Between power and input terminals: 1,500V AC, 1 minute
Between power and transistor output terminals: 1,500V AC, 1 minute
Between power and relay output terminals: 2,300V AC, 1 minute
Between input and transistor output terminals: 1,500V AC, 1 minute
Between input and relay output terminals: 2,300V AC, 1 minute
IEC/EN 61131-2:2007 compliant
35A maximum (Cold start with T
D-type ground (Class 3 ground)
UL1007 AWG16
UL1015 AWG22, UL1007 AWG18
Reverse polarity: Normal operation
Improper voltage or frequency: Permanent damage may be caused
Improper lead connection: Permanent damage may be caused
Approx. 230g
S
AXIS P
/L
U
'
MART
RO
ITE
SER
S
FT1A-
H24RC, B24RC
H40RC, B40RC
41VA
48VA
= 25°C, 200V AC)
a
Approx. 400g
Approx. 580g
M
FT9Y-B1378
ANUAL
H48KC, H48SC
B48KC, B48SC
2
(1G)
43VA
Approx. 540g