Remote I/O Slave

The SmartAXIS can be used as a remote I/O slave by configuring the SmartAXIS as a remote I/O slave in WindLDR. The settings
can be configured in the Remote I/O Slave Configuration dialog box of WindLDR.
Specifications
Network settings
Local Host Port No.
Master communication timeout (Note)
Input settings
Output settings
Number of simultaneously connectable masters
Note: When communication is lost with the remote I/O master for the configured timeout or longer, all outputs of the remote I/O slave are turned
off.
Remote I/O Slave Communication State
The operating status (running/stopped) of the remote I/O slaves cannot be switched. Remote I/O slaves always perform I/O
refresh. While remote I/O slaves have no communication with the remote I/O master, they are in "Disconnected" state and all their
outputs are off. Once the communication is established with the remote I/O master, they are in "Connected" state and the I/O
states start to be exchanged between the master and the slaves.
Status
The communication between the remote I/O master and slave is established.
Connected
The digital inputs and analog inputs of the slave are reflected on the master.
The outputs of the master are reflected to the slave's outputs.
The remote I/O slave is waiting for the communication from the remote I/O master.
Disconnected
The digital inputs and analog inputs of the slave are not reflected on the master.
All outputs of the slave are off.
The communication state with the remote I/O master can be checked with the LED on the SmartAXIS Lite and with the LCD on the
SmartAXIS Pro.
■Lite
The communication state is reflected in the power/run status LED.
Status
Connected
The power/run status LED is on.
Disconnected
The power/run status LED is flashing.
■Pro
The communication state is displayed on the standard screen and the status monitor screen. For how to check the communication
state on the status screen, see "Monitoring the Remote I/O Slave Status" on page 12-9.
Standard screen
Connected
Remote I/O Slave
Connected
12-8
Item
Mode
IP address
Subnet mask
Default gateway
Remote I/O Slave
Disconnected
S
AXIS P
MART
Automatically acquire an IP address/fixed IP address
000.000.000.000 to 255.255.255.255
000.000.000.000 to 255.255.255.255
000.000.000.000 to 255.255.255.255
0 to 65535 (default is 2110)
100 ms to 25,500 ms (100 ms increments)
Analog input settings
FT1A-24: 4 points
FT1A-40: 6 points
FT1A-48: 8 points
None
1
Description
Description
Disconnected
/L
U
'
M
FT9Y-B1378
RO
ITE
SER
S
ANUAL
Description