• PNP Output
Sensor Output
• 2-wire Sensor
Output Terminal Wiring
If output relays or transistors in the SmartAXIS or output modules should fail, outputs may remain on or off. For
•
Caution
output signals which may cause heavy accidents, provide a monitor circuit outside the SmartAXIS.
Connect a fuse to the output module, selecting a fuse appropriate for the load.
•
Use proper wires for output wiring.
•
UL1015 AWG22 or UL1007 AWG18
When equipment containing the SmartAXIS is intended for use in European countries, insert an IEC 60127-approved
•
fuse to each output of every module for protection against overload or short-circuit. This is required when equipment
containing the SmartAXIS is destined for Europe.
When driving an inductive load that emits noise like a magnet or a valve, to reduce noise and protect circuits, use a
•
diode for the output on DC power type models and a surge absorber for the output on AC power type models.
Turn off the power to the SmartAXIS when wiring input/output terminals.
•
Emergency stop and interlocking circuits must be configured outside the SmartAXIS.
•
Use the input/output terminals within the SmartAXIS ratings and specifications.
•
Tighten mounting screws with torque of 0.5N·m (5 gf·cm).
•